7 Technical Information
Model
Occasionally Max. voltage
Operating Voltage Range
MPP Voltage Range (Full Power)
Start Voltage
Rated Voltage
Max. Operating Current
Max. Short Current Capability (Isc)
Number of MPP Trackers
DC Connection Type
Surge Protection
Arc Fault Detection
Max. Apparent Power
Max. Actual Power
Rated Output Power
Max. Output Current
Rated Voltage
AC Voltage Range
Night Time Reactive Power
Operating Frequency Range
Power Factor (Adjustable)
Surge Protection
T.H.D
AC Connection Type
Night Time Consumption *
*
1 Maximum Withstand is 1100Vdc. However, the inverter will stop operating when the PV voltage is above 1000Vdc.
*
2 Ambient < 20°C: 470~860V ; Ambient < 30°C: 470~840V ; Ambient < 40°C: 520~800V
*3 Ambient Temperature < 33°C, DC Input Voltage < 840Vdc
*4 With RS-485 communication
Table 7-1A: Specifications
DC Input
Type II SPD (built-in) ; Type I+II SPD (optional)
AC Output
168 A for 380V / 400V / 440V ; 133 A for 480V
380V / 400V / 440V / 480V, 3Ø3W or 3Ø4W
Terminal block, Max. 240 mm² Cu and Al conductor
4
75
M100A_280 / 284
1100 V *
200 - 1000 V
520 - 840 V *
> 250 V
610 V
30 A / MPPT
50 A / MPPT
8
Amphenol H4 DC Connector
Built-in
110 kVA *
110 kW
100 kW @ 50°C
80% - 120% of nominal AC voltage
60 kVAR
50 / 60Hz ± 5Hz
0.8 ind - 0.8 cap
Type II SPD
< 3% at Rated output current
< 3.5 W