SYS5INST ISS.3 2000

7.0 External Wiring

7.1. Hardwired Sounder

The System 5000 Control Panel includes provision for two hardwired sounder
circuits. The circuitry monitors two pairs of conductors fitted with 4k7 End of Line
resistors. No connection to the control Panel should be made at this stage.

7.2. Hardwired Callpoint

The System 5000 Control Panel includes provision for a hardwired Callpoint
interface. The Control Panel monitors this input via a 4k7 End of Line resistor. No
connection to the Control Panel should be made at this stage.
Note. The external connections & wiring must be tested in the conventional
manner. Under no circumstances should the system circuitry be tested using a
meggar tester, once the connections to the control panel, or peripherals, has been
made.

7.3 Device Wiring

7.3.1. Using an Ohmmeter, check both sounder circuits to ensure that they have a 4.7k
ohm resistance across the connections and that the resistance between each connection
and the Control Panel earth point is greater than 20 M Ohm.
7.3.2. Check any Callpoint external wiring. The resistance across the Callpoint
connection should read 4.7k. Ensure that the resistance between each connection and
the Control Panel earth point is greater than 20 M Ohm.
7.3.3. Once external wiring circuits have been checked, make the connections to the
control panel. The Control Panel should be powered down prior to termination.
Connect all external wiring to the applicable Control Panel terminals (see drawing
p02910). Upon completion of this, repower the Control Panel.