EMS SYSTEM 5000 Installation Manual page 12

Hide thumbs Also See for SYSTEM 5000:
Table of Contents

Advertisement

6.3. When powering up, the following procedure must be followed.
6.3.1. If the panel is switched off, apply the mains power to the unit.
6.3.2. After the system has completed its initialisation sequence, the display will
show, figure 7 followed by figure 8
Warm Start
FIRIS OS V1.6
Figure 7
6.3.3. Connect the batteries (observing the correct polarity).
6.4. When the Control Panel is first powered up, the "Processor Fault" LED will
illuminate and the fault buzzer sound. This continues whilst the system initialises
itself and runs through self-test routines.
6.5. Once initialised, the green "Supply Healthy" LED will illuminate. At this time the
"Processor Fault" LED will also be illuminated, press " silence alarms" followed by
"reset" to clear this LED. The Control Panel will run through a series of diagnostic
self-tests. The illumination of the applicable LED and the sounding of the fault buzzer
will indicate any errors on the display.
6.6. Under normal non-fault conditions, the display will indicate status as "Normal"
(see figure 9). If the keyswitch is left in the "On" position, the display will indicate
that the panel is in "Access mode" (see figure 10).
Searching..........
01 02 03 04 05 06
EMS FIRE SYSTEMS LTD
Status Normal
DATE
Figure 9
EMS FIRE SYSTEMS LTD
Panel in Access
0 FOR ACCESS
Figure 10
11
SYS5INST ISS.3 2000