2.1.2. Installation

Before the installation, check the Installation requirements
chapter.
Full setup scheme:
Figure 1- Scheme of full setup
DANGER
Power supply and digital inputs are not allowed to be
connected during installing and/or wiring of the Sensformer
Connectivity Device!
Risk of electric shock!
DANGER
Power supply is not allowed to be connected to the Sensformer
Connectivity Device without circuit breaker and overcurrent
protection!
Risk of electric shock!
Make sure there is enough space around the device because of
ventilation:
≥50mm above and below
Make sure there is enough space between the Sensformer
Connectivity Device and high voltage and/or warming devices:
≥50mm around
2.1.2.1. Mount the device
Figure 2 - Sensformer Connectivity Device
Attention! Cord or wire not supplied with the equipment.
REQUIREMENT
Above and below the installed device must be get at
least 50 mm free space because of the suitable
ventilation.
REQUIREMENT
High voltage and warming devices cannot be placed
closer than 50 mm for the Sensformer Connectivity
Device.
1. Connect the overcurrent device and the circuit
breaker
DANGER
Power supply and digital inputs are not allowed to be
connected during installing and/or wiring Sensformer
Connectivity Device!
Risk of electric shock!