Installation Guide i-3 Control Technology V2 www.usa.siemens.com/i-3...
Page 2
P1 Panel with i-3 Control Technology V2 between the general information Dangerous Procedures DANGER contained in this publication and the In addition to other procedures Hazardous voltage. contents of drawings or supplementary described in this manual as dangerous, Will cause death or...
Should further information be desired or should particular problems arise which are not covered suffi ciently for the purchaser’s purposes, the matter should referred to the local Siemens sales offi ce. The contents of this instruction manual shall not become part of or modify any prior of existing agreement, commitment or relationship.
Chapter 1 Introduction Overview The principal standards which apply are: • Siemens i-3 Control Technology V2 is a National Electric Code NFPA 70 • Siemens P1 Series Panel integrated with NEMA PB1, NEMA 250 • i-3 Control Technology V2 components.
Chapter 1 Introduction Parts illustration Figure 1.2 below shows the front view of P1 panel with i-3 Control Technology V2 components. Mounting hole (4X) Box (can) Location of Main breaker or main lugs Data rail BQD breaker SIPOD Neutral lugs...
• The i-3 V2 Controller immediately of any damage. all items have been received. The P1 • Power supply (inside the i-3 V2 Controller) Lighting Panel with i-3 Control Technology • Controller fuse (inside the i-3 V2 5. Arrange for a carrier inspection of...
Note: Estimated weight is for panelboard with all the circuits filled with breakers and SIPODs. Storage If the P1 Series Lighting Panel with i-3 Control Technology V2 is not installed and energized immediately, it should be stored in a clean dry area where a uniform temperature prevents condensation.
Preparation for installation For installation/replacement of i-3 Control DANGER Prior to installation of the panel, study Technology V2 in Siemens P1 panel, the this instruction manual and the drawing following conditions have to be met: Hazardous voltage. package, such as general arrangement,...
Figure 3.1 Illustrates the parts included in the panel interior and how they are arranged. i-3 V2 interior Deadfront Trim/Door Enclosure Controller Controller Access Figure 3.1 Panel Assembly Note: If hardware is damaged or lost, contact Siemens technical assistance with hardware specifi cations.
If the i-3 Control Technology V2 Figure 3.4 shows the location for the components need to be installed in low voltage conduit entry access on i-3 the panel, please refer to the step-by-step V2 controller. installation instructions described on...
For complete detail on i-3 V2 controller to closing of the panel. refer to Breaker rating label located configuration, refer to i-3 V2 I/O Controller – on the face of the breaker. Modbus, PN LVIN-MODCO-0212; or for 2. Be sure all breakers extend properly...
Disconnect and lock off all non-power-limited fire alarm circuit For Controllers without touch screen power before working on conductors, and medium power (I/O Controller) - A computer with the i-3 this equipment. network-powered broadband V2 software Configurator Tool is required Overview communications cables.
Chapter 6 System components BQD circuit breaker description Figure 6.1 and 6.2 show the layout of the BDQ circuit breaker. Breaker Handle Load Side Mounting Figure 6.1 BQD 15A Breaker Side View BQD Line Connection Load Lug Terminal Figure 6.2 BQD 15A Breaker Top View Catalog Numbers Interrupting Ratings...
Page 16
Chapter 6 System components Figure 6.3 BQD 15A and SIPOD Assembly – Top View Figure 6.4 Two-pole SIPOD – Top View Figure 6.5 Two-pole BQD and two-pole SIPOD Assembly – Top View...
Chapter 6 System components DANGER Breaker Hazardous voltage. Will cause death or serious injury. Keep out. Barrier Qualifi ed personnel only. Disconnect and lock off all power before working on this equipment. Load Side Mounting Installing BQD circuit breakers into the P1 panel 1.
SIPOD assembly. Code, 700.12(F). Note: This is not a field modification option. The i-3 V2 system with this option should be ordered with this modification. An i-3 V2 system with emergency lighting circuits can have 2, 4, 6, 8, 10 or 12 circuits factory modified for this application.
Page 19
Chapter 6 System components The factory modified panelboard is clearly marked for the location of emergency lighting circuits controls. Figure 6.10 shows the panel deadfront with the labels clearly showing the emergency lighting circuits locations. For label 1, see Figure 6.11; for label 2, see Figure 6.12.
Page 20
Consult instruction sheet 11-B-1021-01. located in pocket behind door or cover, before installation or maintenance. For replacement instructions, please call the Sales Offi ce at 1-800-427-2256. Siemens Industry, Inc. Norcross, GA 11-C-1050-01 Rev.1 Figure 6.12 Label 2...
Page 21
Chapter 6 System components 18 circuit panel 18 circuit panel 30 circuit panel 30 circuit panel 30 circuit panel 30 circuit panel with two with four with two with four with six with eight emergency emergency emergency emergency emergency emergency lights circuits lights circuits lights circuits...
SIPOD description SIPOD is a remotely operated electro- mechanical contactor device that is attached to Siemens BQD molded case circuit breaker. The purpose of a SIPOD is to allow switching of a load, ON and OFF, from a remote location or according to a pre-arranged time schedule.
Chapter 6 System components Figures 6.14 and 6.15 are images of a one pole SIPOD. D. SIPOD Load Lug C. Manual Override E. SIPOD A. Tang/Conductor Connector B. Mechanical Status Figure 6.14 Indicator SIPOD – Top View Figure 6.15 SIPOD – Side View Figure 6.16 Two-pole SIPOD Components...
Page 24
Chapter 6 System components A. Tang/Conductor tab D. SIPOD load lug Tang/conductor tab electrically connects The SIPOD load lug is identical to the BQD the circuit breaker to the SIPOD. To ensure circuit breaker load lug. As a result, it can a secure connection, the tang must be receive the same type and size of wire as inserted into the load lug of the circuit...
2. Remove the P1 Panel trim and deadfront. 3. Verify that the circuit breaker is a Siemens Type BQD rated 15, 20, 25 Tang or 30 amps. Type and rating information is located on the circuit breaker label.
Chapter 6 System components DANGER Data Rail Description The data rail is a shielded communication Hazardous voltage. bus that connects up to 21 SIPODs Will cause death or depending on the size of the panelboard. serious injury. Keep out. There are two data rails on a P1 Lighting Qualifi...
3. Follow these guidelines for data rail orientation. a. Be sure the data rail PCB is facing upward. b. The ribbon connector must be positioned on the i-3 V2 controller side. Figure 6.22 Opening the Data Rail Lid 4. Loosen the screws (2 total) that secure the data rail lid as shown in Figure 6.22...
Chapter 6 System components DANGER Hazardous voltage. Will cause death or serious injury. Keep out. Qualifi ed personnel only. Disconnect and lock off all power before working on this equipment. Neutral extensions description The neutral extension are adapter pieces that mount to the neutral of the panel. These parts provide additional neutral connections when the SIPODs partially cover the normal neutral lugs.
Page 29
Back View of i-3 V2 Controller Fuse is LittleFuse KLDR002 Power Fuse switch For more detailed information about EIB choke the i-3 V2 Controller configuration Surge protection (C/C only) and set-up procedures, please refer circuit to the i-3 V2 Controller User Guide...
Disconnect and lock off all for Controller power before working on Bracket this equipment. Installing the i-3 V2 controller 1. Disconnect and lock off all power sources supplying this panel. 2. Remove the P1 Panel trim and Figure 6.27 deadfront.
- Red wire from bus bar on phase A - Green wire from ground 5. Remove the mounting screws (4 total) 6. Remove the i-3 V2 controller Ribbon cables description The ribbon cable is a 26-wire flat connector used to connect the I/O Board and the data rail.
Figure 6.31 i-3 V2 Controller with Cover Removed Note: Do not force the ribbon cable connector in the wrong orientation as it could damage the plastic and cause the I/O Board to malfunction.
Appendix A P1 with i-3 Control Technology V2 panel specifi cation The table below lists the specifi cations of a P1 with i-3 Control Technology V2 Table A1 panel specifi cations Max voltage 480Y/277V AC Max System 1-Phase, 3-Wire 3-Phase, 4-Wire...
Appendix B i-3 Control Technology V2 spare parts For an i-3 Control Technology V2 replacement parts list, please refer to i-3 V2 Replacements parts publication. Appendix C Customer service support information Siemens Industry, Inc. Building Technologies Division 5400 Triangle Parkway...