Manual for installation of the Sensformer® Connectivity Device
WARNING
Set the ModBus settings always accordingly the sensors used.
Bad settings can cause incorrect requests.
NOTE
When set the ModBus sensors, always use the "+" button! If
the last line of the ModBus configuration table is set sensor,
then the last sensor data will be lost during the save!
Use the
button even after setting the last sensor except
the 300th!
Clicking on the sensor ID, the read data will be shown.
Figure 40 - ModBus sensor data
To return the ModBus page use the "Back to the config" button.
The Sensformer Connectivity Device can store 3000 requested
ModBus sensor data.
6.2.2.6. Settings
On the Settings sheet, the main firmware and data processing
parameters can be configured. After saving the modifications, the
affected services are automatically restarted.
Figure 41 - Settings page
Analog sensors:
Figure 42- Analog sensors on Settings page
Gain and offset: calibration properties of the analog input
channel
Unit: unit of the measured value of the connected sensor
(e.g. A, V, °C)
Type: operation mode of the input channel (4-20 mA or +-20
mA).
Digital sensors:
Figure 43- Digital sensors on Settings page
Threshold: The voltage limit value of the logical 1 level.
Below this level the input signal is considered as logical „0",
above as logical „1".
Type: operation mode if the digital input channel: DC or AC.
System:
Figure 44- System on Settings page
© 2020 Siemens Energy
Page 32