Manual for installation of the Sensformer® Connectivity Device
Figure 8- Example for connecting ModBus
2
Size of conductor: 1.5 mm
.
Tightening torque: < 1Nm.
Cable: double insulated, UL 94 V-1 flammability classification and
VW-1 flame rating.
2
Ferrule: certified, 1.5 mm
conductor area with 14 mm overall
length and 8 mm pin length.
Connector pins:
D+: data plus line
D-: data minus line,
COM: internal common reference point of Sensformer
Connectivity Device.
7. Connect digital inputs
DANGER
The digital inputs are not allowed to be powered when
installing and/or wiring Sensformer Connectivity Device.
Risk of electric shock!
REQUIREMENT
Do not use cables without ferrules. The ferrules must be
certified.
For
more
information,
requirements chapter.
REQUIREMENT
The using cables on the digital inputs must be double insulated
and must
have UL 94 V-1 flammability classification and VW-1
flame
rating.
For
more
information,
requirements chapter.
Connect the digital sensors to the digital inputs of the Sensformer
Connectivity Device. D1A and D1B, D2A and D2B are
interchangeable connections.
see
the
Installation
see
the
Installation
© 2020 Siemens Energy
NOTE
Though, the digital inputs are interchangeable, the measured
values are not in DC mode. Because of that, the recommended
wiring is the following: the D2B and D1B are the negative, the
D2A and D1A are the positive in DC mode.
This has no effect to the AC mode.
Figure 9 – Example for connecting digital inputs
2
Size of conductor: 1.5 mm
.
Tightening torque: < 1Nm.
Cable: double insulated, UL 94 V-1 flammability classification and
VW-1 flame rating.
2
Ferrule: certified, 1.5 mm
conductor area with 16-18 mm overall
length and 8 mm pin length.
8. Connect the power supply
WARNING
PE marked connector does NOT provide PROTECTIVE
BONDING PROTECTION, its purpose is FUNCTIONAL EARTH
TERMINAL!
DANGER
Be sure to disconnect the power cord before installing and or
wiring Sensformer Connectivity Device.
Risk of electric shock!
The power supply of Sensformer Connectivity
pole screw terminal (PE, L and N). In case AC power supply is the
L and N terminal are polarity independent, and must be wired up
the PE.
REQUIREMENT
The color of PE cable must be green-yellow.
For
more
information,
requirements chapter.
Device
has a three-
see
the
Installation
Page 10