Manual for installation of the Sensformer® Connectivity Device
REQUIREMENT
Do not use the cables without ferrules! The ferrules must be
certified!
For
more
information,
requirements chapter.
REQUIREMENT
The using cables on the power supply must be double insulated
and must
have UL 94 V-1 flammability classification and VW-1
flame
rating.
For
more
information,
requirements chapter.
2
Size of conductor: 1.5 mm
.
Tightening torque: < 1Nm.
Cable: double insulated, UL 94 V-1 flammability classification and
VW-1 flame rating.
2
Ferrule: certified, 1.5 mm
conductor area with 16-18 mm overall
length and 8 mm pin length.
During the wiring make sure that the PE is break last. The PE cable
must be longer with 2-3 cm like the L an N cables. The diameter
of used PE cable must be 1.5mm
see
the
Installation
see
the
Installation
2
.
© 2020 Siemens Energy
Page 11