Status - 1 byte
0x00 = Date and time configured and verified
0x01 = Month bad
0x02 = Day bad
0x04 = Year bad
0x10 = Hour bad
0x20 = Minutes bad
0x40 = Seconds bad
0xff = Save problem
Set Relay State - 0x5F
This command allows you to configure the relay states. The relays are normally de-energized,
and can be configured to operate in the energized fail-safe condition. When the relays are
latched, they are cleared by operator intervention. Non-latching relays are cleared automatically
once the concentration decreases below the alarm level threshold, or the fault is corrected
without operator intervention.
Command packet to instrument:
Command Code (0x5F) - 1 byte
Relay Flags - 1 byte
bit 0: Relay state
0 = De-energized
1 = Energized
bit 1: Relay latching state
0 = Non-latching
1 = Latching
bits 2-7: Undefined
Response packet from instrument:
Command Code (0x5F) - 1 byte
VC4™ Date - 2 bytes
VC4™ Time - 2 bytes
Status - 1 byte
0x00 = relays state set
0xff = Error, relays state not changed
VC4™
163
User Manual