Service Menu; Parameters - Ferroli TOR Instruction For Installation And Maintenance

Wall-mounted electric boiler
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1

1.3 SERVICE MENU

To access the menu, keep the button
when the panel is faulty).
The display shows
(parameters) and it is possible to go to another menu
(
/
by pressing

1.3.1 Parameters

If the display shows
The flashing symbol
To scroll the list of parameters, press the buttons
To check the displayed parameter value, press the button
and confirm with the button
button
repeatedly to return to the initial display.
Parameters table
Parameter
Parameter name
P01
Water pump post-circulation
P02
Heating On temperature
P03
Water pressure switch type
P04
Storage tank On temperature
P05
Storage tank
Offset temperature for room
P06
compensation control
P07
Room compensation curve
P08
DHW
P09
A08 Fault detection option
Comfort heating mode (heat balance
P10
option)
P11
Air Venting Function
P12
Sterilization temperature
P13
Anti-legionella function period
EN
10
pressed for at least 5 seconds in any status (except for parameter setting or
)
.
, the list of parameters can be accessed by pressing the button
, appears, indicating the display of the first parameter.
within a few seconds. The flashing parameter will appear again (e.g.
Interval
(1 - 20 minutes)
5 - 20 °C
0 - 1
5 - 10 °C
0 - 1
30 - 50
0 - 10
1 - 6
00: No detection
03: Detection
00 - 01
0 - 1
55 - 70 °C
1 - 31 days
cod. 3542B750 - Rev 09 - 02/2024
(
)
/
.
. To change the value, press the buttons
Default value
20
8 °C
0
5 °C
0
30
0
6 - 12 KW= 3
18 - 24 KW= 6
00
00
0
65 °C
7
(faults history) or
.
/
Description
When the heating temperature goes below the
Set Point - P02, the heating elements are enabled for
activation
0 = on/off
1 = sensor type
When the storage tank temperature goes
below the
Set Point - P04, the heating elements are
enabled for activation
0 = external storage tank disabled
1 = external storage tank enabled
(1.2.10.1 on page 9)
0: No external compensation control
1~10: Compensation curve C01-C10
Defines the maximum number of elements in
operation.
00 = comfort
01 = heat balance
(1.2.5.1 on page 8)
1 = manual activation of Air Venting function
The temperature reached by the anti-legionella
function
Anti-legionella function interval days
TOR
(reset faults)
(
)
). Press the

Advertisement

Table of Contents
loading

Table of Contents