1.5 SERVICE MENU

To enter on the service menu press the "back" key
state or when the panel breaks down).
The display show
(parameters) and it can be changed into other menu
(
/
pressing

1.5.1 Parameters

When the display show
The symbol flashing appears
Parameter code Parameter name
P01
Water pump post-circulation
P02
Switch on heating temperature 5 - 20 °C
P03
Water switch type
P04
Switch on tank temperature
P05
Storage tank
Offset temperature of heating
P06
room compensation control
Compensating curve of heating
P07
outdoor compensation control
P08
Maximum power
P09
A08 Fault defection option
Heating comfort mode (heat
P10
balance option)
P11
Air Purge function
P12
Sterilization temperature
P13
Water tank sterilization period
Note: Manually exit from the set state after setting and power down the system after waiting for a while (generally 3-6s
because the system is saving the parameter) because the system saves the parameter under the non-set state, or
the parameter won't be saved. The outdoor temperature compensation setting is also subject to the restriction.
Example: how to modify the P02 value
x5 s
10
EN
)
it is possible to enter on the parameter code by pressing the
, meaning the first parameter is show: to check the value press the
Range
(1 - 20 minutes)
0 - 1
5 - 10 °C
0 - 1
30 - 50
0 - 10
1 - 6
00: No detection
03: Detection
00 - 01
0 - 1
55 - 70 °C
1 - 31 days
cod. 3542B750 - Rev 05 - 07/2022
for at least 5 seconds under any state (except for parameter setting
Default value Remark
20
8 °C
0
5 °C
0
30
0
6 - 12 KW= 3
18 - 24 KW= 6
00
00
0
65 °C
7 days
(fault history) or
(reset faults) by
key.
When the heating temperature is below the
Set Point - P02, the heating elements are
enabled to start
0 = on/off
1 = sensor type
When the tank temperature is below the
Set Point - P04, the heating elements are
enabled to start
0 = external tank disabled
1 = external tank enabled
(1.4.9.1 on page 9)
0: No outdoor compensation control
1~10: Compensating curve C01-C10
It defines the maximum number of the wor-
king elements.
00 = comfort
01 = heat balance
(1.4.5.1 on page 8)
1 = activate the Air Purging function manually
This is the temperature at whitch the boiler is
load during the sterilization function
Period for this function
TOR
key.