Regulation Parameter Table For The Pump Unit - Elsteam EHPN Series Operating And Maintenance Manual

High-pressure air humidifiers
Table of Contents

Advertisement

Description of columns in the Table of Parameters
• Par.:Listofconfigurabledeviceparameters;
• Description: Indicates parameter operation and any possible selections;
• MU: Measurement unit relating to the parameter;
• Range: Describes the interval of values that the parameter can assume. This can be correlated with other instrument
parameters (indicated with the parameter code).
NOTE: if the actual value is outside the permitted limits for that parameter (for example, because other parameters
defining the aforementioned limits have been altered), the value of the violated limit is displayed instead of the actual
value;
• Default:Indicatesthepre-setfactoryconfiguration;
• PW: Indicates the access level for the parameter:
• U=Userparameters;
• M=Maintenanceparameters.

11.1 Regulation parameter table for the pump unit

Par. Description
SETPOINT group
SP1 Humidity only setpoint P25=0.
SP4 Pressure setpoint.
CONFIGURATION group
Operating mode (see "10.2 HUMIDITY REGULATION" ON PAGE 78)
CFGp
0-1 (0) =ON/OFFfromdigitalinput;
HUM (1)=Humiditysensor.
P1
Electrical conductivity of the water.
S2 sensor type (pressure transducer).
0-10(1)=Proportionalinput0...10V;
P2
0-5(2)=Proportionalinput0...5V;
0.20(3)=Input0...20mA;
4.20(4)=Input4...20mA;
P3
S2 minimum value (pressure transducer).
P4
S2 maximum value (pressure transducer).
P5
S2 sensor offset (pressure transducer).
P6
S1 sensor offset (temperature).
S3 sensor type.
0-10(1)=Proportionalinput0...10V;
0-5(2)=Proportionalinput0...5V;
P7
0.20(3)=Input0...20mA;
4.20(4)=Input4...20mA;
E520(5)=EVHTP520proprietaryprobe.
P8
S3 minimum value (if CFGp=HUM).
P9
S3 maximum value (if CFGp=HUM).
P10 S3 humidity sensor offset (if CFGp=HUM).
P13 Number of nozzles on last branch (highest).
Nozzle capacity.
P14
0=4l/h;1=8l/h.
Temperature unit of measure (changing value means that the temperature
P21
parameter limits will need to be reset manually). 0=°C;1=°F.
P22 Steam production unit of measurement. 0=kg/h;1=lb/h.
P25 Racknumber.
REGULATION group
r0
Standard pressure setpoint hysteresis (SP4).
r1
Minimum value for setting humidity setpoint.
r2
Maximum value for setting humidity setpoint.
r4
Humidity proportional band.
c4
Range to reach outlet pressure.
MAINTENANCE/ALARMS group
M0
Lowpumptemperaturealarmthreshold.Thehysteresisisfixedat2°C/°F.
924EHPNE4.01 - EHPN series humidifiers
|87|Configurationparameters|
MU
Range
Default
%
r1...r2
bar
70...90
---
0-1 / HUM
µS/cm
0...1500
0-10 / 0-5 /
---
0.20 / 4.20
bar
0...200
bar
0...200
bar
-10...10
°C/°F
-10.0...10.0
0-10 / 0-5 /
---
0.20 / 4.20 /
0-10
E520
%rH
0...100
%rH
0...100
%rH
-10...10
num
1...100
---
0/1
---
0/1
---
0/1
num
0...3
%
0...10
%
0...r2
%
r1...100
%
0...50
s
10...90
°C/°F
0.0...30.0
PW
70.0
U
80
M
0-1
U
100
M
4.20
M
0
M
200
M
0
M
0.0
M
M
0
M
100
M
0
M
1
M
1
M
0
M
0
M
1
M
5
U
20
M
95
M
10
M
60
M
7.0
M
02/2024