Technical Specifications - Elsteam EHPN Series Operating And Maintenance Manual

High-pressure air humidifiers
Table of Contents

Advertisement

2.1 Technical specifications

Description
Steam production
Production capacity:
Electrical properties
Power absorbed:
Power supply:
Single phase/three phase:
Water properties
Supply water quality:
Supply water conductivity:
Supply water hardness:
Minimum inlet flow rate:
Supply water temperature
Supply water pressure:
Water outlet pressure:
Supply water connection:
General specifications
Dimensions:
Weight (pump unit):
IP protection level of the
pump unit:
IP protection level of the
distributionrack:
Maximum installation
altitude:
Ambient conditions of the pump unit
Ambient operating
conditions:
Transportation and storage
conditions:
Ambient conditions of the distribution rack
Ambient operating
conditions:
Transportation and storage
conditions:
Regulation
Control type/command
signal:
Supervision/Configuration:
Compliance
EC:
VDI6022-1:
NOTE: Contact the ELSTEAM sales office for further information.
924EHPNE4.01 - EHPN series humidifiers
EHPN
EHPN
M.U.
060
120
l/h
60
120
kW
1.5
1.5
V,Hz
Ph
---
μS*cm
°f
l/min
°C(°F)
MPa
(bar)
MPa
(bar)
---
mm (in.)
kg
---
---
m (ft.)
°C(°F),%
°C(°F),%
°C(°F),%
°C(°F),%
---
---
---
---
EHPN
EHPN
EHPN
180
240
300
180
240
300
1.5
1.5
1.5
230 Vac 50/60Hz
Single-phase
See section "WATER SPECIFICATIONS" ON PAGE 33
0...100
0...5
2x production capacity
4...50 (39.2..122)
0.05...0.4 (0.5...4)
8 (80)
M3/4 G
See section "4.1 DIMENSIONS" ON PAGE 22
44
IP20
IP40
2000 (6561.6)
1...40(33.8...104),10...80%non-condensing
-10...70(14...185),5...95%non-condensing
-10...40(14...104),10...80%non-condensing
-20...70(-4...185),5...95%non-condensing
ON/OFF
Proportional
Probe
RS-485 MODBUS
SupervisionWi-Fi
Yes,withself-certification
See certificate
| 18 | Technical data |
EHPN
EHPN
EHPN
420
540
660
420
540
660
1.5
2.2
2.2
EHPN
840
840
2.2
02/2024

Advertisement

Table of Contents
loading