Elsteam ZEPHYR OEM Operating And Maintenance Manual

Immersed electrode humidifiers for air handling units
Table of Contents

Advertisement

Quick Links

ZEPHYR OEM
Immersed electrode humidifiers for air handling units
Operating and maintenance manual
924EHKOE4.00 - 07/2024
WARNING
Make sure you read and fully
understand the manual before
using this device.
Non-observance of these
instructions may result in death
or serious injury.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ZEPHYR OEM and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Elsteam ZEPHYR OEM

  • Page 1 ZEPHYR OEM Immersed electrode humidifiers for air handling units WARNING Make sure you read and fully understand the manual before using this device. Non-observance of these instructions may result in death Operating and maintenance manual or serious injury. 924EHKOE4.00 - 07/2024...
  • Page 2: Table Of Contents

    1.6.4  Plumbing components ..........................14 1.7  Steam distributor/humidifier configuration table ................14 2. TECHNICAL DATA ...........................15 2.1  Technical specifications ........................15 2.1.1 ExtraSmall models | Zephyr OEM......................15 2.1.2 Small models | Zephyr OEM........................16 2.1.3 Medium models | Zephyr OEM........................17 2.1.4  Large models | Zephyr OEM........................18 3. RECEIVING THE PRODUCT ......................19 3.1 ...
  • Page 3 7.2.4  Manual draining ............................36 7.2.5 Menu ................................37 7.2.6 User Menu ..............................38 7.2.7 Maintenance menu............................39 7.2.8  Displaying/resetting the operating hours ....................40 7.2.9 Output functional test ..........................41 8. POWER-UP AND START-UP ......................42 8.1 First start-up instructions ........................42 924EHKOE4.00 - Zephyr OEM humidifiers | 3 | Contents | 07/2024...
  • Page 4 11.7 Modbus addresses ..........................55 11.7.1 Modbus address table ..........................55 11.7.2 Modbus resource table ..........................58 12. DIAGNOSTICS ..........................61 12.1 Zephyr OEM alarms table........................61 13. MAINTENANCE ..........................66 13.1 Before you start ..........................66 13.2 Introduction to maintenance ......................66 924EHKOE4.00 - Zephyr OEM humidifiers...
  • Page 5 14.1 Hydraulic unit ............................71 14.2 Electrical part ............................73 15. WIRING DIAGRAMS ........................74 15.1  Wiring diagram for 230 Vac models ....................74 15.2  Wiring diagram for 400/460 Vac 3Ph models .................75 16. SELECTING AND DEFINING THE MODEL ..................76 16.1 Introduction ............................76 16.2  Procedure for selecting and defining the model ................76 924EHKOE4.00 - Zephyr OEM humidifiers | 5 | Contents | 07/2024...
  • Page 6: Important Information

    Liability and residual risks ELSTEAM assumes no liability for any damage caused by the following (by way of example; this is not an exhaustive list): • Installation/use for purposes other than those specified and, in particular, not adhering to the safety provisions set out by current regulations in the country in which the product is installed and/or contained in this manual;...
  • Page 7: Important Safety Information

    UNAUTHORISED PERSONNEL The humidifier must not be used by persons (including children) with reduced physical, sensory or mental capabilities or persons with no experience or knowledge. 924EHKOE4.00 - Zephyr OEM humidifiers | 7 | Important safety information | 07/2024...
  • Page 8: Safety Information Relating To The Product

    SAFETY INFORMATION RELATING TO THE PRODUCT ZEPHYR OEM series humidifiers are defined as "NOT ACCESSIBLE TO THE PUBLIC". Before carrying out any work on the equipment, read these instructions carefully, making sure you understand everything. DANGER RISK OF ELECTRIC SHOCK, EXPLOSION OR ELECTRIC ARC •...
  • Page 9: Safety Information Related To Health And Hygiene

    SAFETY INFORMATION RELATED TO HEALTH AND HYGIENE The Zephyr OEM humidifier features: • Automatic draining for inactivity; • Periodic automatic cleaning; • Plastic material on whose surface bacterial colonies do not proliferate. Inadequate use and/or poor maintenance of the humidifier can damage your health.
  • Page 10: Introduction

    The Zephyr OEM humidifier is inserted into the compartment provided, which is NOT ACCESSIBLE to the public, not exposed to the weather and therefore protected. To prevent ice from forming during winter if the unit is installed outside, use heating cables for the water supply and outlet pipes.
  • Page 11: Main Features

    • Advanced error diagnostics; • Operating time counter. • Remote supervision with EPoCA (optional via EVIF25 interface). 1.4 Applications The Zephyr OEM series is mainly used in applications requiring sterile steam, including: • Data centres; • Industrial plants; • Offices;...
  • Page 12: Available Configurations

    Medium kit, 5 kg/h, 230 Vac, single-phase EHKO015T0M Zephyr OEM M immersed electrode humidifier, 10–15 kg/h, 400/460 Vac Medium kit, 10 kg/h, 400 Vac, three-phase EHKO015T0M Zephyr OEM M immersed electrode humidifier, 10–15 kg/h, 400/460 Vac Medium kit, 10 kg/h, 460 Vac, three-phase EHKO015T0M Zephyr OEM M immersed electrode humidifier, 10–15 kg/h, 400/460 Vac Medium kit, 15 kg/h, 400 Vac, three-phase...
  • Page 13: Accessories

    1.6 Accessories The following accessories are available for use with Zephyr OEM series immersed electrode humidifiers: 1.6.1 Linear distributors Description EHSD040T Linear steam distributor, 400 mm (1.31 ft). EHSD060T Linear steam distributor, 600 mm (1.97 ft). EHSD080T Linear steam distributor, 800 mm (2.62 ft).
  • Page 14: Sensors And Control Accessories

    EHSDC038 EHSDW022 NOTE: The • symbol indicates that the data applies to every p/n (X/T); contact the ELSTEAM sales office for further information. (*) = Use 2 EHSD040• + 1 EHSDY038 manifold (**) = Use 2 EHSD060• + 1 EHSDY038 manifold (***) = Use 2 EHSD080•...
  • Page 15: Technical Data

    2. TECHNICAL DATA 2.1 Technical specifications 2.1.1 ExtraSmall models | Zephyr OEM... Description EHKO00000XS EHKO002M0XS EHKO003T0XS Steam production Production capacity: kg/h 2...3 Pressure limits: Pa/bar 500/0.005 Steam connection diameter: mm (in.) 38 (1.50) Electrical properties Power absorbed: 1.5...2.2 2.25 Configurable...
  • Page 16: Small Models | Zephyr Oem

    2.1.2 Small models | Zephyr OEM... Description EHKO00000S EHKO003M0S EHKO005T0S EHKO008T0S Steam production Production capacity: kg/h 3...8 Pressure limits: Pa/bar 500/0.005 Steam connection diameter: mm (in.) 22 (0.87) Electrical properties Power absorbed: 2.2...6 3.75 Configurable Configurable Configurable Power supply: 230 Vac...
  • Page 17: Medium Models | Zephyr Oem

    2.1.3 Medium models | Zephyr OEM... Description EHKO00000M EHKO005M0M EHKO015T0M Steam production Production capacity: kg/h 5...15 10...15 Pressure limits: Pa/bar 500/0.005 Steam connection diameter: mm (in.) 38 (1.50) Electrical properties Power absorbed: 3.75...11.5 3.75 7.5 / 11.5 Configurable Configurable Power supply:...
  • Page 18: Large Models | Zephyr Oem

    NOTE: Models with dual hydraulic units can be created by adding an expansion to the control board, in which case the aforementioned values become the sum of those for the 2 hydraulic units chosen. 924EHKOE4.00 - Zephyr OEM humidifiers | 18 | Technical data |...
  • Page 19: Receiving The Product

    • Open the cardboard boxes, removing the corner protectors; • Take the hydraulic unit, current sensor (TA) and control board out of their packaging. 3.1.2 Checking the packaging contents The product packaging contains: • Zephyr OEM series humidifier, consisting of: • Hydraulic unit; • Instruction sheet. 924EHKOE4.00 - Zephyr OEM humidifiers...
  • Page 20: Dimensions And Mechanical Assembly

    4. DIMENSIONS AND MECHANICAL ASSEMBLY 4.1 Dimensions 4.1.1 Hydraulic unit S Models XS models L Models M Models Fig. 2. Hydraulic unit dimensions 924EHKOE4.00 - Zephyr OEM humidifiers | 20 | Dimensions and mechanical assembly | 07/2024...
  • Page 21: Zephyr Oem Kit

    Electrodes Electric outlet pump Maximum level sensor Water outlet circuit (not supplied) Water filling pipe (not supplied) Steam outlet pipe (can be purchased as an accessory) 924EHKOE4.00 - Zephyr OEM humidifiers | 21 | Dimensions and mechanical assembly | 07/2024...
  • Page 22: Installation Hole Spacing

    [mm (in.)] [mm (in.)] [mm (in.)] ExtraSmall 254 (10.0) Small 314 (12.36) 140 (5.51) 106 (4.17) Medium 374 (14.72) Large 493.5 (19.42) 240 (9.45) 110 (4.33) 924EHKOE4.00 - Zephyr OEM humidifiers | 22 | Dimensions and mechanical assembly | 07/2024...
  • Page 23: Installing The Plumbing

    5. INSTALLING THE PLUMBING 5.1 Before you start Zephyr OEM series humidifiers are defined as "NOT ACCESSIBLE TO THE PUBLIC". WARNING REGULATORY INCOMPATIBILITY Make sure all the equipment used and systems designed conform to current local, regional and national standards.
  • Page 24: Installing The Plumbing

    If using metal pipes, make sure they are properly earthed. Do not use pre-existing system pipework or used materials. Only use the materials supplied or, where appropriate, the products supplied by ELSTEAM as accessories (see"1.6 ACCESSORIES" ON PAGE 13). NOTE: if using a pressure reducer, make sure is it effective and does not cause drastic pressure drops when the mains pressure is very low.
  • Page 25: Water Drainage System

    If the installation fails to meet these specifications, install a water and limescale drain tank at the bottom of the humidifier (p/n EHVI) (contact the Elsteam sales office for further information). Tank specifications • Outlet diameter 38 mm (1.50 in.);...
  • Page 26: Steam Distribution

    NOTE: in ambient temperature conditions which may lead to the formation of ice, it is wise to take all necessary precautions to prevent the supply water and the drain water from freezing and causing the humidifier to malfunction. 924EHKOE4.00 - Zephyr OEM humidifiers | 26 | Installing the plumbing |...
  • Page 27: Electrical Connections

    • Before applying the power supply, check all the wiring connections. • Do not connect cables to unused terminals and/or terminals marked with the text “No connection” (N.C.). 924EHKOE4.00 - Zephyr OEM humidifiers | 27 | Electrical connections | 07/2024...
  • Page 28: Dimensioning Electrical Components

    (**) Temperatures up to 40°C – 24 Vac contactor coil – Check the offsets at 55 and 70°C, and size in accordance with current regulations (***) L = 2 m maximum voltage drop of 0.2 V (#) P/n 0103349007 924EHKOE4.00 - Zephyr OEM humidifiers | 28 | Electrical connections | 07/2024...
  • Page 29: Electrical Connections

    ON = Termination resistor enabled; off = Disabled. Termination resistor on CANBUS serial line. 24-25 Digital input: humidistat (CFG = 0-1) (S0) TERM2 ON = Termination resistor enabled; off = Disabled. 924EHKOE4.00 - Zephyr OEM humidifiers | 29 | Electrical connections | 07/2024...
  • Page 30: Power Supply And Earth Wiring Connection

    6.4.2 Power supply and earth wiring connection DANGER RISK OF ELECTRIC SHOCK Make sure that the entire system is earthed to the highest standards. 924EHKOE4.00 - Zephyr OEM humidifiers | 30 | Electrical connections | 07/2024...
  • Page 31: Configurations

    CV input = Closed 0/1 input = Closed Fig. 10. Humidity sensor connection (CFG = HUM) NOTE: To start humidity production, the CV and 0/1 contacts must be closed. 924EHKOE4.00 - Zephyr OEM humidifiers | 31 | Electrical connections | 07/2024...
  • Page 32: Evhtp520 Humidity Sensor Connection (Cfg = Hum And Cfg = Huml)

    CV input = Closed 0/1 input = Closed Fig. 13. Humidity sensor connection 0...5 V / 0...10 V NOTE: To start humidity production, the CV and 0/1 contacts must be closed. 924EHKOE4.00 - Zephyr OEM humidifiers | 32 | Electrical connections | 07/2024...
  • Page 33: Temperature Sensor Connection (Cfg = 1T)

    Set to ON if connected to the expansion, but only if it is TERM1 ON = Termination resistor enabled; off = Disabled. the first or last element wired in the network. 924EHKOE4.00 - Zephyr OEM humidifiers | 33 | Electrical connections | 07/2024...
  • Page 34: User Interface (Optional)

    Make sure the humidifier and all the installed components are properly connected before start-up, in accordance with regulations, criteria and all applicable local, regional and national standards. 7.1 User interface Fig. 16. Zephyr OEM humidifier user interface (optional) 7.1.1 Icons Icon Lit steadily Icon Lit steadily •...
  • Page 35: First Start-Up

    Fig. 20. Home screen with proportional regulation (CFG = PROP) Top line: Actual humidity request in %. NOTE: The CV and 0/1 contacts must be closed to produce humidity. 924EHKOE4.00 - Zephyr OEM humidifiers | 35 | User interface (optional) | 07/2024...
  • Page 36: Changing The Main Sensor Humidity Setpoint

    With CFG = 1T or CFG = 2T only. To change the temperature setpoint: Touch and release Fig. 24. Changing the temperature setpoint 7.2.4 Manual draining To start manual draining: Fig. 25. Manual draining 924EHKOE4.00 - Zephyr OEM humidifiers | 36 | User interface (optional) | 07/2024...
  • Page 37: Menu

    Access the user menu Access the maintenance technician menu RESERVED. NOT ACCESSIBLE TO THE PUBLIC. Currently accessing alarm control Access the alarm log Reset parameters to factory settings 924EHKOE4.00 - Zephyr OEM humidifiers | 37 | User interface (optional) | 07/2024...
  • Page 38: User Menu

    Humidity limit setpoint See "9.10 TABLE OF ADJUSTMENT PARAMETERS" ON PAGE 50 Sets the temperature setpoint (wellness application). Temperature setpoint See "9.10 TABLE OF ADJUSTMENT PARAMETERS" ON PAGE 50 924EHKOE4.00 - Zephyr OEM humidifiers | 38 | User interface (optional) | 07/2024...
  • Page 39: Maintenance Menu

    ON = Inlet solenoid valve output ON. Displays the status of the outlet pump. Outlet pump status OFF = Outlet pump output OFF; ON = Outlet pump output ON. 924EHKOE4.00 - Zephyr OEM humidifiers | 39 | User interface (optional) | 07/2024...
  • Page 40: Displaying/Resetting The Operating Hours

    Outlet pump hours Displays the hours of outlet pump operation. Fan hours Displays the operating hours of the fans. Reset operating hours  The operating hours can be reset by setting the parameters to 0. 924EHKOE4.00 - Zephyr OEM humidifiers | 40 | User interface (optional) | 07/2024...
  • Page 41: Output Functional Test

    ON = Fan output forced ON. Forces the general alarm output on/off. General alarm output OFF = General alarm output forced OFF; status ON = General alarm output forced ON. 924EHKOE4.00 - Zephyr OEM humidifiers | 41 | User interface (optional) | 07/2024...
  • Page 42: Power-Up And Start-Up

    (including the bacteria that cause Legionellosis) may proliferate and be transferred into the air treatment system. • The humidifier must be used correctly and be maintained and cleaned properly at the prescribed intervals, as described in the MAINTENANCE chapter. 924EHKOE4.00 - Zephyr OEM humidifiers | 42 | Power-up and start-up | 07/2024...
  • Page 43: Starting Up After A Seasonal Or Long-Term Shut-Down

    The humidifier cyclically carries out a full wash and then restarts with a lower frequency. Operation has been developed to ensure maximum energy efficiency and optimal water use. 924EHKOE4.00 - Zephyr OEM humidifiers | 43 | Power-up and start-up |...
  • Page 44: Operation

    • Enable digital input closed (CV); • Remote ON/OFF digital input closed (0/1). When the S0 digital input is closed, the Zephyr OEM generates humidity at the maximum value set in parameter r6. 9.2.2 Proportional regulation | CFG = PROP To use the Zephyr OEM with proportional regulation, the following conditions must be met: •...
  • Page 45: Regulation With The Humidity Sensor | Cfg = Hum

    9.2.3 Regulation with the humidity sensor | CFG = HUM To use the Zephyr OEM with regulation based on a humidity sensor, the following conditions must be met: • CFG = HUM or CFG = HUML; • Set parameter P2 according to the sensor type to be used;...
  • Page 46: Regulation With The Humidity Sensor + Limit Sensor | Cfg = Huml

    9.2.4 Regulation with the humidity sensor + limit sensor | CFG = HUML To use the Zephyr OEM with regulation based on a humidity sensor and limit sensor, the following conditions must be met: • CFG = HUML; • Set parameter P2 according to the sensor type to be used; • Set parameter P7 according to the limit sensor type to be used;...
  • Page 47: Regulation With A Temperature Probe | Cfg = 1T

    The electrical conductivity of the water tends to rise while producing humidity because it concentrates the substances in the water, and consequently the times mentioned above tend to reduce; during this stage, the Zephyr OEM activates the outlet pump until the internal current drops below the threshold set in parameter c6.
  • Page 48: Time-Based Water Dilution

    If there is no foam in the boiler, the Zephyr OEM resumes normal operation. If the level sensor is reached again within time c12, there is foam in the boiler. The Zephyr OEM empties the boiler completely. Thereafter, if the following occurs within time c12: •...
  • Page 49: Operating Hours

    9.8 Operating hours The Zephyr OEM records the hours of humidifier operation to allow periodic maintenance. The following times are monitored: • Total hours of machine operating; this cannot be reset and shows the hours of humidifier operation; • Partial hours of hydraulic unit operation; this can be reset after maintenance on the tank;...
  • Page 50: Configuration Parameters

    P11 TA sensor K (1000 = current multiplier of 1.000). 0...2000 1000 Ventilation presence (enables maintenance management based on utility No/Yes operating hours). No = No ventilation; Yes = Ventilation present. 924EHKOE4.00 - Zephyr OEM humidifiers | 50 | Configuration parameters | 07/2024...
  • Page 51 M13 Operating hours threshold for valve maintenance warning. hx10 100..2000 1000 M14 Operating hours threshold for pump maintenance warning. hx10 100..2000 1000 M15 Operating hours threshold for fan maintenance warning. hx10 100..2000 1000 924EHKOE4.00 - Zephyr OEM humidifiers | 51 | Configuration parameters | 07/2024...
  • Page 52 Modbus stop bit. 0 = 1 stop bit; 1 = 2 stop bits. PASSWORD group PA1 First level password. 0 = No password -99...999 PA2 Second level password. -99...999 924EHKOE4.00 - Zephyr OEM humidifiers | 52 | Configuration parameters | 07/2024...
  • Page 53: Modbus Rtu Functions And Resources

    The Modbus registers for the device are organised around the four types of basic data reference indicated above, and this type of data is further identified by the first number of the address. 924EHKOE4.00 - Zephyr OEM humidifiers | 53 | Modbus rtu functions and resources |...
  • Page 54: Available Modbus Commands And Data Areas

    • SHORT = 16 bit with sign • WORD = 16 bit • Byte = 8 bit • The “n” bits = 0...15 bit depending on the value of “n” 924EHKOE4.00 - Zephyr OEM humidifiers | 54 | Modbus rtu functions and resources | 07/2024...
  • Page 55: Modbus Addresses

    P10 Offset of sensor S3 (if CFG = HUML). 2015 SHORT -10...10 Ventilation presence (enables maintenance management 2077 1 BIT based on utility operating hours). 924EHKOE4.00 - Zephyr OEM humidifiers | 55 | Modbus rtu functions and resources | 07/2024...
  • Page 56 Operating hours threshold for partial boiler maintenance 2046 ... hours DWORD 100..2000 warning. 2047 Operating hours threshold for full boiler maintenance 2048 ... hours DWORD 100..2000 warning. 2049 924EHKOE4.00 - Zephyr OEM humidifiers | 56 | Modbus rtu functions and resources | 07/2024...
  • Page 57 0 = 1 stop bit; 1 = 2 stop bits. PASSWORD group PA1 First level password. 0 = No password. 2061 SHORT -99...999 PA2 Second level password. 2062 SHORT -99...999 924EHKOE4.00 - Zephyr OEM humidifiers | 57 | Modbus rtu functions and resources | 07/2024...
  • Page 58: Modbus Resource Table

    PackedAlarm2 Status of alarm AL26. 1 BIT PackedAlarm2 Status of alarm AL27. 1 BIT PackedAlarm2 Status of alarm AL28. 1 BIT PackedAlarm2 Status of warning W29. 1 BIT 924EHKOE4.00 - Zephyr OEM humidifiers | 58 | Modbus rtu functions and resources | 07/2024...
  • Page 59 0.0 ... 6553.5 -3276.8 ... actProd Actual steam production. 1303 R/W SHORT Y kg/h 3276.7 limH Humidity limit sensor status (ON/OFF). 1304 R/W 1 BIT 924EHKOE4.00 - Zephyr OEM humidifiers | 59 | Modbus rtu functions and resources | 07/2024...
  • Page 60 R/W DWORD --- h x 10 429496729.5 MBS_SwEn On/Off command from BMS. 1922 R/W 1 BIT (*) Calculation of operating hours Operating hours = (HIGH register x 65536) + LOW register 924EHKOE4.00 - Zephyr OEM humidifiers | 60 | Modbus rtu functions and resources | 07/2024...
  • Page 61: Diagnostics

    12. DIAGNOSTICS The table below lists alarms with corresponding solutions. Indication takes place via the alarm LED and the buzzer. Each alarm is recorded in the alarm log. 12.1 Zephyr OEM alarms table Code Description Cause Effects Solution • Overcurrent between the •...
  • Page 62 • Probe not connected properly • Humidifier OFF • Change the sensor type sensor S1 • Incorrect probe type • AL14 recorded in the log • Check for electrical noise 924EHKOE4.00 - Zephyr OEM humidifiers | 62 | Diagnostics | 07/2024...
  • Page 63 (only on humidifier and master humidifier humidifier are switched off (slaves master humidifier slave) when nTyP ≠ 0 operate as stand-alone) • Automatic reset • AL24 recorded in the log 924EHKOE4.00 - Zephyr OEM humidifiers | 63 | Diagnostics | 07/2024...
  • Page 64 • Alarm relay ON • Clean the pump, outlet hydraulic unit • W32 recorded in the log manifold and outlet circuit • Replace the outlet pump if it is not working 924EHKOE4.00 - Zephyr OEM humidifiers | 64 | Diagnostics | 07/2024...
  • Page 65 • Check for leaks 2 pump operation > M14 • No effect on regulation • Replace the outlet pump if maintenance • AL37 recorded in the log necessary • Reset the counter 924EHKOE4.00 - Zephyr OEM humidifiers | 65 | Diagnostics | 07/2024...
  • Page 66: Maintenance

    • The humidifier frequently drains the water completely to dilute it and perform a complete wash; Zephyr OEM series humidifiers normally renew the water in the boiler in a balanced way, optimising efficiency while reducing the risk of malfunction in relation to the amount of steam produced.
  • Page 67: Checking The Status Of The Humidifier

    • In the event of water leakage, disconnect the humidifier power supply immediately. • If any adverse event not described in this documentation arises, carry out maintenance and/or replace the boiler. Plus, contact ELSTEAM customer service for the relevant guidelines and instructions; DANGER RISK OF ELECTRIC SHOCK, EXPLOSION OR ELECTRIC ARC If an adverse event occurs, disconnect the humidifier power supply immediately.
  • Page 68: Cleaning The Boiler

    DANGER LOOSE WIRING CAUSES ELECTRIC SHOCKS AND OVERHEATING Tighten the connections in compliance with the technical specifications relating to tightening torques. Fig. 36. Cleaning the boiler 924EHKOE4.00 - Zephyr OEM humidifiers | 68 | Maintenance | 07/2024...
  • Page 69: Replacing The Boiler

    Tighten the connections in compliance with the technical specifications relating to tightening torques. Fig. 37. Replacing the boiler 13.5.1 Tightening torque for electrode connections Boiler Nuts Spanner Tightening torque 3...15 kg/h 2.5 Nm 20...40 kg/h SW10 4 Nm 924EHKOE4.00 - Zephyr OEM humidifiers | 69 | Maintenance | 07/2024...
  • Page 70: Fitting The Boiler

    DANGER LOOSE WIRING CAUSES ELECTRIC SHOCKS AND OVERHEATING Tighten the connections in compliance with the technical specifications relating to tightening torques. 13.7 Cleaning/replacing the electrodes 924EHKOE4.00 - Zephyr OEM humidifiers | 70 | Maintenance | 07/2024...
  • Page 71: Spare Parts

    14. SPARE PARTS 14.1 Hydraulic unit Fig. 38. Spare parts for Zephyr OEM series - Plumbing Part 924EHKOE4.00 - Zephyr OEM humidifiers | 71 | Spare parts | 07/2024...
  • Page 72 Cleanable boiler for low-conductivity, EHKT0K44 Electrode kit for EHBK005TLCS EHBK040TLCL 20–30–40 kg/h, three-phase models EHKT0K45 Electrode kit for EHBK003T00XS EHKT0K46 Electrode kit for EHBK003THCXS EHKT0K47 Electrode kit for EHBK003TLCXS 924EHKOE4.00 - Zephyr OEM humidifiers | 72 | Spare parts | 07/2024...
  • Page 73: Electrical Part

    14.2 Electrical part Fig. 39. Electrical spare parts for Zephyr OEM Ref. Description EHHKT011P4 Complete control unit 924EHKOE4.00 - Zephyr OEM humidifiers | 73 | Spare parts | 07/2024...
  • Page 74: Wiring Diagrams

    15. WIRING DIAGRAMS 15.1 Wiring diagram for 230 Vac models The customer is responsible for connecting the transformer/contactor/fuse holder. POWER SUPPLY Fig. 40. Wiring diagram for models EHKO003 / EHKO005 924EHKOE4.00 - Zephyr OEM humidifiers | 74 | Wiring diagrams | 07/2024...
  • Page 75: Wiring Diagram For 400/460 Vac 3Ph Models

    15.2 Wiring diagram for 400/460 Vac 3Ph models The customer is responsible for connecting the transformer/contactor/fuse holder. POWER SUPPLY Fig. 41. Wiring diagram for models EHKO003 / EHKO005 / EHKO010 / EHKO020 924EHKOE4.00 - Zephyr OEM humidifiers | 75 | Wiring diagrams | 07/2024...
  • Page 76: Selecting And Defining The Model

    • Humidifier Model phases: Displays the number of power supply phases for the selected humidifier (read-only); • Humidifier Model power supply: Displays the power supply type for the selected humidifier (read-only); • Humidifier Model type: Displays the selected humidifier series (read-only). 924EHKOE4.00 - Zephyr OEM humidifiers | 76 | Selecting and defining the model | 07/2024...
  • Page 77 60 = EHKO008T4 12 = EHKO030T4 13 = EHKO040T4 14 = EHKO050T4 15...17 = Reserved NOTE: Do not enter values marked as RESERVED in the table above. 924EHKOE4.00 - Zephyr OEM humidifiers | 77 | Selecting and defining the model | 07/2024...
  • Page 78 7. The procedure takes a few seconds to complete. Please wait. When the procedure is complete, the description of the configured model will appear in the Humidifier Model field. 8. Procedure finished. 924EHKOE4.00 - Zephyr OEM humidifiers | 78 | Selecting and defining the model | 07/2024...
  • Page 79 This page has been left blank on purpose. 924EHKOE4.00 - Zephyr OEM humidifiers | 79 | 07/2024...
  • Page 80 This document and the solutions contained within it are the intellectual property of ELSTEAM, safeguarded by the Italian Industrial Property Code (CPI). ELSTEAM forbids the reproduction and distribution, even in part, of the contents, unless express authorisation is obtained directly from ELSTEAM.