The voltage average is made available as a standardised 16-bit-value with a resolution of 10 mV.
Example: measuring value operating voltage = 2512 ➞ real measuring value = 25.12 Volt

7.3.22 Maximum Voltage REX12D/REX22D

Register 4(01...16)17 for channel 1 - 16, readable, functional code 3.
Contains the highest measured voltage of the channel since the last reset.
value range: 0 - 65535 (equals 0.0 – 655.35 V)
data length: 1 word
Byte (LOW)
bit 7
description
128
value
0/1
Byte (HIGH)
bit 15
description
32768
value
0/1
Table 19: Maximum voltage REX12D/REX22D
The maximum voltage is made available as a standardised 16-bit-value with a resolution of 10 mV.
Example: measuring value operating voltage = 2512 ➞ real measuring value = 25.12 Volt.

7.3.23 Minimum Voltage REX12D/REX22D

Register 4(01...16)18 for channel 1 - 16, readable, functional code 3.
Contains the highest measured voltage of the channel since the last reset.
value range: 0 - 65535 (equals 0.0 – 655.35 V)
data length: 1 word
Byte (LOW)
bit 7
description
128
value
0/1
Byte (HIGH)
bit 15
description
32768
value
0/1
Table 20: Minimum voltage channel
The minimum voltage is made available as a standardised 16-bit-value with a resolution of 10 mV.
Example: measuring value operating voltage = 2512 ➞ real measuring value = 25.12 Volt
34
bit 6
bit 5
bit 4
64
32
16
0/1
0/1
0/1
bit 14
bit 13
bit 12
16384
8192
4096
0/1
0/1
0/1
bit 6
bit 5
bit 4
64
32
16
0/1
0/1
0/1
bit 14
bit 13
bit 12
16384
8192
4096
0/1
0/1
0/1
bit 3
bit 2
bit 1
8
4
2
0/1
0/1
0/1
bit 11
bit 10
bit 9
2048
1024
512
0/1
0/1
0/1
bit 3
bit 2
bit 1
8
4
2
0/1
0/1
0/1
bit 11
bit 10
bit 9
2048
1024
512
0/1
0/1
0/1
bit 0
1
0/1
bit 8
256
0/1
bit 0
1
0/1
bit 8
256
0/1

Advertisement

Table of Contents
loading

Table of Contents