Status Circuit Protector - E-T-A ControlPlex EM12D-TMB Instruction Manual

Table of Contents

Advertisement

value range: 0 – 65535
data length: 1 word
value
Definition
[dec.]
0
DEVICE IS OPERATING PROPERLY
1
MAINTENANCE REQUIRED
2
OUT OF SPECIFICATION
3
FUNCTIONAL CHECK
4
DEVICE FAILURE
Table 7: Status of interface module

7.3.4 Status Circuit Protector

Register 47201 – 47216 for channel 1 - 16, only readable, functional code 3.
Status for each electronic circuit protector is cyclically transmitted to the interface module. Individual status
information is shown in the following table.
value range: 0 – 65535
data length: 1 word
Word
description
value
load output (ON/OFF)
short circuit
overload
reserve
reserve
reserve
limit value (reached/
exceeded)
hardware lock (OFF
at the device itself)
Word
description
value
24
bit 7
bit 6
bit 5
128
64
32
0/1
0/1
0/1
0/1*
0/1*
0/1*
bit 15
bit 14
bit 13
32768
16384
8192
0/1
0/1
0/1
explanation
In all other events this value is transmitted
This value is transmitted if one of the circuit protectors
tripped due to short circuit or overload
This value is transmitted if one of the circuit protectors de-
tected an undervoltage
Not supported
This value is transmitted if one of the connected circuit pro-
tectors has set the error-bit in the ELBus
bit 4
bit 3
bit 2
16
8
4
0/1
0/1
0/1
0/1*
0/1*
0/1*
bit 12
bit 11
bit 10
4096
2048
1024
0/1
0/1
0/1
®
Device Status.
bit 1
bit 0
2
1
0/1
0/1
0/1*
0/1*
bit 9
bit 8
512
256
0/1
0/1

Advertisement

Table of Contents
loading

Table of Contents