4.5 Operating Mode: Faultless Operation

If there is neither a critical nor a non-critical failure and if there is a connection to the superordinate control unit, the
Modbus controller will change into the operating mode "faultless operation". The parameters will be transmitted
from the superordinate control unit to the Modbus controller and will be saved there. Subsequently they will be for-
warded to the electronic circuit protectors. The slot configuration data and slot parameters will be exchanged over
Modbus Register between the superordinate control unit and the Modbus controller.

4.6 Operating Mode: Bootloader

ControlPlex
®
Views tool allows putting the Modbus Controller into the bootloader mode and to load a new firm-
ware. The actual procedure is described in a separate document.

4.7 Signalling of the Various Operating Modes

The different operating modes of the Modbus controller are indicated as follows:
Operating mode
system start of supply module
independent operation
faultless operation
critical failure detected
uncritical failure detected
uncritical failure detected
bootloader active
Table 1: Available operating modes
Indication of operating mode
LED CE/CM
green blinking
green
red
yellow
yellow blinking
red blinking
Modbus communication
not defined
not available
available
not available
available
not available
not available
11