7.3.6 System Commands EM12D-TMB

Register 46001, writable, functional code 6.
Depending to transmitted value one of following functions will be executed.
7.3.6.1 Reset to Factory Settings
Set Value 130 at Register load default Parameter at supply modul.
7.3.6.2 Reset Statistical Information
Set Value 250 at Register reset all Statisticinformation at all channels. It is equally possible to reset these pieces of
information channel-wise. This is described in the chapter of the action commands.

7.3.7 Diagnostic Information of the Intelligent Interface Module EM12D-TMB

Register 46002, readable, functional code 3.
The following global errors and diagnostic messages are returned. Evaluation is bit-wise.
value range: 0 – 65535
data length: 1 word (unsigned integer)
Byte [0]
description
TN_SysNoConfig
TN_SysConfigMismatch
TN_SysQueueFull
TN_ELBusDown
26