Bertazzoni Professional Series Installation, User And Maintenance Manual page 20

Freestanding dual fuel ranges, gas worktop, electric self clean oven
Hide thumbs Also See for Professional Series:
Table of Contents

Advertisement

GAS CONNECTION
Natural gas 4.0" iwc
LP/Propane 10.0" iwc.
Incoming line pressure upstream from the regulator must
be 1" iwc higher than the manifold pressure in order to
check the regulator.
The regulator used on this range can withstand a maximum
input pressure of 1/2 PSI (13.8" iwc or 3.5 kPa). If the line
pressure exceeds that amount, a stepdown regulator is
required.
The appliance, its individual shut-off valve, and the
pressure regulator must be disconnected from the gas line
during any pressure testing of that system at pressures in
excess of 1/2 PSI (13.8" iwc or 3.5 kPa).
The individual manual shut-off valve must be in the OFF
position during any pressure testing of the gas supply
piping system at test pressures equal to or less than 1/2
PSI (13.8" iwc or 3.5 kPa).
WARNING
Before carrying out any servicing operation
disconnect the appliance from gas and
electric supply and extra appliance from
final installation place in order to have
access to the appliance for proper servicing
intervention.
!
1) Range cooker gas pipe gas entry
2) Pressure regulator
20
1
2
IMPORTANT
Fig. 13
PRESSURE REGULATOR MUST BE
MOUNTED
WITH
POINTING IN THE DIRECTION OF
GAS FLOW!
INCORRECT MOUNTING MAY CAUSE
PERFORMANCE ISSUES AND MAY
CONSTITUTE A GAS HAZARD.
ISSUES DERIVED FROM INCORRECT
INSTALLATION
OF
REGULATOR ARE NOT COVERED
UNDER
WARRANTY.
THE
ARROW
PRESSURE
MANUFACTURER