7. Fault

7.1 Fault analysis

If the control system recognises a fault, this is
shown on the display by a number with an "F"
in front of it. If a 3-way switch with filter status
display is installed, the LED on the 3-way
switch also starts to flash.
The fault F9 is shown here as an example.
That means that there is a fault in the cabling
to the outside temperature sensor or in the
sensor itself.
The unit stays in fault mode until the
corresponding problem has been resolved.
Then the unit carries out an automatic reset
(Autoreset) and the display reverts to
operational mode.
The table in section 7.3 contains an overview
of the faults, the possible causes and the
measures that need to be taken.

7.2 Filter status display

If the message "FIL" appears in the display,
the filters have to be exchanged.
After changing the filters, the filter status
display has to be reset by pressing the "OK"
button.
The display "FIL" flashes briefly and then the
display reverts to operational mode.