Check the actual state of the connected binary inputs.
Measure output contacts using the voltage drop method of applying at least the minimum
contact load given for the output relays in the technical data, for example 100 mA at 24 V
AC/DC.
A
GUID-BBAEAF55-8D01-4711-A71D-BBC76B60BA3D V1 EN-US
Figure 10: Testing output contacts using the voltage drop method
1
2 Contact voltage drop
3 Load
4 Supply voltage
Busbar protection REB650
Commissioning manual
Change the parameter
3PhaseAnalogGroup/SMAI_20_n:1 (n= the number of the SMAI used).
Changing the
skills.
In PCM600, change the parameter
under the parameter settings for each current input.
In LHMI, select Main menu/Tests/I/O modules. Then navigate to the board with the
actual binary input to be checked.
With PCM600, right-click the product and select Signal Monitoring. Then navigate to the
actual I/O board and to the binary input in question. The activated input signal is
indicated with a yellow-lit diode.
Output relays, especially power output relays, are designed for breaking high
currents. Due to this, layers of high resistance may appear on the surface of
the contacts. Do not determine proper functionality of connectivity or contact
resistance by measuring with a regular hand-held ohm meter.
V
1
4
Contact current
© Copyright 2013 ABB. All rights reserved
Negation in Configuration/Analog modules/
Negation parameter is not recommended without special
CTStarPointn (n= the number on the current input)
2
3
Section 9
Troubleshooting