To Install The Outdoor Unit; To Provide Drainage - Daikin Altherma EHFH03S18D 3V Series Installer's Reference Manual

Table of Contents

Advertisement

7
|
Unit installation

7.3.4 To install the outdoor unit

7.3.5 To provide drainage

Installer reference guide
66
(mm)
a 100 mm above expected level of snow
Make sure that condensation water can be evacuated properly.
Install the unit on a base to make sure that there is proper drainage in order to
avoid ice accumulation.
Prepare a water drainage channel around the foundation to drain waste water
away from the unit.
Avoid drain water flowing over the footpath, so that it does NOT become slippery
in case of ambient freezing temperatures.
If you install the unit on a frame, install a waterproof plate within 150 mm of the
bottom side of the unit in order to prevent water from getting into the unit and
to avoid drain water dripping (see the following figure).
4× M8/M10
ERLA03D + EHFH03S18D
Daikin Altherma 3 R F
4P596806-1C – 2022.09

Advertisement

Table of Contents
loading

This manual is also suitable for:

Altherma erla03d v3 series

Table of Contents