Daikin Altherma EHFH03S18D 3V Series Installer's Reference Manual page 123

Table of Contents

Advertisement

ERLA03D + EHFH03S18D
Daikin Altherma 3 R F
4P596806-1C – 2022.09
The other user interface is set to At unit.
Space heating/cooling: Number of LWT zones
#
Code
[A.2.1.8]
[7-02]
The system can supply leaving water to up to 2 water temperature zones. During
configuration, the number of water zones must be set.
1 LWT zone:
There is only 1 leaving water temperature zone. This zone is called the main leaving
water temperature zone.
a Main LWT zone
2 LWT zones:
There are 2 leaving water temperature zones:
The zone with the lowest leaving water temperature (in heating) is called the
main leaving water temperature zone.
The zone with the highest leaving water temperature (in heating) is called the
additional leaving water temperature zone.
Remark: In practice, the main leaving water temperature zone consists of the
higher load heat emitters and a mixing station is installed to achieve the desired
leaving water temperature.
a Additional LWT zone
b Main LWT zone
c Mixing station
Description
Number of LWT zones
0 (1 LWT zone)
1 (2 LWT zones)
a
a
c
b
10
Configuration
|
Installer reference guide
123