Daikin EHBH04DA6V Installation Manual
Daikin EHBH04DA6V Installation Manual

Daikin EHBH04DA6V Installation Manual

Daikin altherma - low temperature split
Hide thumbs Also See for EHBH04DA6V:
Table of Contents

Advertisement

Installation manual

Daikin Altherma – Low temperature split
EHBH04DA6V
EHBH08DA6V
EHBH08DA9W
EHBX04DA6V
Installation manual
EHBX08DA6V
English
Daikin Altherma – Low temperature split
EHBX08DA9W

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EHBH04DA6V and is the answer not in the manual?

Questions and answers

Summary of Contents for Daikin EHBH04DA6V

  • Page 1: Installation Manual

    Installation manual Daikin Altherma – Low temperature split EHBH04DA6V EHBH08DA6V EHBH08DA9W EHBX04DA6V Installation manual EHBX08DA6V English Daikin Altherma – Low temperature split EHBX08DA9W...
  • Page 2 3P507286-1...
  • Page 3: Table Of Contents

    Detailed screen with weather-dependent curve..17 Daikin website (publicly accessible). 5.2.8 Configuration wizard: Tank ......... 17 ▪ The full set of latest technical data is available on the Daikin Settings menu ................18 extranet (authentication required). 5.3.1 Main zone ..............18 5.3.2...
  • Page 4: About The Box

    WARNING WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable The appliance shall be stored in a room without legislation (for example national gas regulation) and are continuously operating ignition sources (example: open executed only by authorised persons.
  • Page 5 Indoor unit Room where the indoor unit is installed. ▪ "8.5  Table 3 – Minimum venting opening area for natural Room adjacent to room A. ventilation: indoor unit" on page 26. EHBH/X04+08DA Installation manual Daikin Altherma – Low temperature split 4P495266-1 – 2017.06...
  • Page 6: Preparing Water Piping

    Normal kWh rate power 6.3 A Opening the units supply Optional equipment 4.1.1 To open the indoor unit 3‑way valve 100 mA 1 Remove the upper front panel. Installation manual EHBH/X04+08DA Daikin Altherma – Low temperature split 4P495266-1 – 2017.06...
  • Page 7: Mounting The Indoor Unit

    Optional: If you want to fix the unit to the wall from inside the unit, provide an additional screw plug. 2 Lift the unit. EHBH/X04+08DA Installation manual Daikin Altherma – Low temperature split 4P495266-1 – 2017.06...
  • Page 8: Connecting The Refrigerant Piping

    4 In case of connection with the optional domestic hot water tank, see the installation manual of the domestic hot water tank. NOTICE Install air purge valves at all local high points. Installation manual EHBH/X04+08DA Daikin Altherma – Low temperature split 4P495266-1 – 2017.06...
  • Page 9: To Connect The Drain Hose To The Drain

    20  mm to prevent condensation on the surface of the insulation. Connecting the electrical wiring DANGER: RISK OF ELECTROCUTION WARNING ALWAYS use multicore cable for power supply cables. EHBH/X04+08DA Installation manual Daikin Altherma – Low temperature split 4P495266-1 – 2017.06...
  • Page 10: To Connect The Main Power Supply

    Interconnection cable (=main power supply) supply with a system impedance Z less than or equal to Normal kWh rate power supply Preferential power supply contact Installation manual EHBH/X04+08DA Daikin Altherma – Low temperature split 4P495266-1 – 2017.06...
  • Page 11: To Connect The Shut-Off Valve

    X5M/6 and X5M/4; the negative polarity to X5M/5 and 3~, 50 Hz X5M/3. L1 L2 L3 230 V AC 1 Connect the electrical meters cable to the appropriate terminals as shown in the illustration below. EHBH/X04+08DA Installation manual Daikin Altherma – Low temperature split 4P495266-1 – 2017.06...
  • Page 12: To Connect The Domestic Hot Water Pump

    1 Connect the power consumption digital inputs cable to the 1 Connect the space cooling/heating ON/OFF output cable to the appropriate terminals as shown in the illustration below. appropriate terminals as shown in the illustration below. Installation manual EHBH/X04+08DA Daikin Altherma – Low temperature split 4P495266-1 – 2017.06...
  • Page 13: To Connect The Safety Thermostat (Normal Closed Contact)

    You can change the user permission level as follows: 2 Reinstall the switch box cover and close the switch box. 1 Go to [B]: User profile 3 Reinstall the upper front panel. EHBH/X04+08DA Installation manual Daikin Altherma – Low temperature split 4P495266-1 – 2017.06...
  • Page 14: Configuration Wizard

    NOT higher than 70°C. 01 20 6 Press the left dial to confirm the new setting. 7 Press the center button to go back to the home screen. Installation manual EHBH/X04+08DA Daikin Altherma – Low temperature split 4P495266-1 – 2017.06...
  • Page 15: Configuration Wizard: Backup Heater

    ▪ For a 9W model, it is fixed to 400V, 3ph. Code Description [9.3.2] [5‑0D] ▪ 0: 230V, 1ph ▪ a: Main LWT zone ▪ 1: 230V, 3ph ▪ 2: 400V, 3ph EHBH/X04+08DA Installation manual Daikin Altherma – Low temperature split 4P495266-1 – 2017.06...
  • Page 16: Configuration Wizard: Main Zone

    50°C, In External room thermostat control, unit operation is decided by the Daikin recommends NOT to disable the backup heater external thermostat or equivalent (e.g. heat pump convector). second step because it will have a big impact on the...
  • Page 17: Configuration Wizard: Additional Zone

    The weather-dependent curves are defined by two setpoints: ▪ Setpoint (X1, Y2) EHBH/X04+08DA Installation manual Daikin Altherma – Low temperature split 4P495266-1 – 2017.06...
  • Page 18: Settings Menu

    You can set additional settings using the main menu screen and its submenus. The most important settings are presented here. 5.3.1 Main zone Thermostat type Only applicable in external room thermostat control. Installation manual EHBH/X04+08DA Daikin Altherma – Low temperature split 4P495266-1 – 2017.06...
  • Page 19: Menu Structure: Overview Installer Settings

    [9.B] Sensors External sensor Sensor offset Averaging time [9.C] Bivalent Bivalent Boiler efficiency Temperature Hysteresis INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. EHBH/X04+08DA Installation manual Daikin Altherma – Low temperature split 4P495266-1 – 2017.06...
  • Page 20: Commissioning

    The pressure relief valve purges water when opened. The minimum water volume is guaranteed in all conditions. See "To check the water volume" in "3.2 Preparing water piping" on page 6. Installation manual EHBH/X04+08DA Daikin Altherma – Low temperature split 4P495266-1 – 2017.06...
  • Page 21: To Perform An Operation Test Run

    Also avoid disturbances in the water circuit during the operation manual. test run. ▪ Shut off valve test ▪ Diverter valve test ▪ Bivalent signal test ▪ Alarm output test EHBH/X04+08DA Installation manual Daikin Altherma – Low temperature split 4P495266-1 – 2017.06...
  • Page 22: Technical Data

    8 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin extranet (authentication required). Piping diagram: Indoor unit...
  • Page 23: Wiring Diagram: Indoor Unit

    Field supply Position in switch box Position in switch box Translation of text on wiring diagram Legend English Translation (1) Main power connection (1) Main power connection Main PCB EHBH/X04+08DA Installation manual Daikin Altherma – Low temperature split 4P495266-1 – 2017.06...
  • Page 24 Only for wired On/OFF For safety thermostat For safety thermostat thermostat thermostat Inrush Inrush current Only for wireless On/OFF Only for wireless On/OFF thermostat thermostat Max. load Maximum load Installation manual EHBH/X04+08DA Daikin Altherma – Low temperature split 4P495266-1 – 2017.06...
  • Page 25 2 core Power limitation 2x0.75 A8P: X801M: 4-5 demand input 4 A11P: X21: 1-2 A14P: P1-P2 user interface signal communication 2 core 2x0.75 A13P: P1-P2 LAN adapter communication 4D111879B EHBH/X04+08DA Installation manual Daikin Altherma – Low temperature split 4P495266-1 – 2017.06...
  • Page 26: Indoor Unit

    Table 3 – Minimum venting opening area for natural ventilation: indoor unit dm=m –m (kg) Minimum venting opening area (cm H=1150 mm H=1200 mm H=1300 mm H=1400 mm H=1500 mm H=1600 mm H=1700 mm H=1800 mm 1.80 1.60 1.40 1.20 1.00 0.80 0.60 0.40 0.20 Installation manual EHBH/X04+08DA Daikin Altherma – Low temperature split 4P495266-1 – 2017.06...
  • Page 27 If dm=1.55  kg, consider the value that corresponds to "dm=1.6 kg". EHBH/X04+08DA Installation manual Daikin Altherma – Low temperature split 4P495266-1 – 2017.06...
  • Page 28 4P495266-1 0000000U 4P495266-1 2017.06...

This manual is also suitable for:

Ehbh08da6vEhbx08da6vEhbx04da6vEhbh08da9wEhbx08da9w