Daikin Altherma EHFH03S18D 3V Series Installer's Reference Manual page 211

Table of Contents

Advertisement

4/8
Field settings table
Breadcrumb
Field code
Setting name
└─ Pwr consumpt. Control
A.6.3.1
[4-08]
Mode
A.6.3.2
[4-09]
Type
A.6.3.3
[5-05]
Amp. value
A.6.3.4
[5-09]
kW value
└─ Averaging time
A.6.4
[1-0A]
└─ Ext amb. sensor offset
A.6.5
[2-0B]
└─ Emergency
A.6.C
└─ Disable protective Function
A.6.D
Disable protections
└─ Overview settings
A.8
[0-00]
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
A.8
[0-01]
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
A.8
[0-02]
High ambient temp. for LWT add zone heating WD curve.
A.8
[0-03]
Low ambient temp. for LWT add zone heating WD curve.
A.8
[0-04]
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
A.8
[0-05]
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
A.8
[0-06]
High ambient temp. for LWT add zone cooling WD curve.
A.8
[0-07]
Low ambient temp. for LWT add zone cooling WD curve.
A.8
[0-0B]
Leaving water value for high ambient temp. for DHW WD curve.
A.8
[0-0C]
Leaving water value for low ambient temp. for DHW WD curve.
A.8
[0-0D]
High ambient temp. for DHW WD curve.
A.8
[0-0E]
Low ambient temp. for DHW WD curve.
A.8
[1-00]
Low ambient temp. for LWT main zone heating WD curve.
A.8
[1-01]
High ambient temp. for LWT main zone heating WD curve.
A.8
[1-02]
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
A.8
[1-03]
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
A.8
[1-04]
Weather dependent cooling of the main leaving water temperature zone.
A.8
[1-05]
Weather dependent cooling of the additional leaving water temperature zone
A.8
[1-06]
Low ambient temp. for LWT main zone cooling WD curve.
A.8
[1-07]
High ambient temp. for LWT main zone cooling WD curve.
A.8
[1-08]
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
A.8
[1-09]
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
A.8
[1-0A]
What is the averaging time for the outdoor temp?
A.8
[1-0B]
What is target delta T in heating?
A.8
[1-0C]
What is the desired delta T in heating for the additional zone?
A.8
[1-0D]
What is the desired delta T in cooling for the main zone?
A.8
[1-0E]
What is the desired delta T in cooling for the additional zone?
A.8
[2-00]
When should the disinfection function be executed?
A.8
[2-01]
Should the disinfection function be executed?
A.8
[2-02]
When should the disinfection function start?
A.8
[2-03]
What is the disinfection target temperature?
A.8
[2-04]
How long must the tank temperature be maintained?
A.8
[2-05]
Room antifrost temperature
A.8
[2-06]
Room frost protection
4P596814-1B - 2022.09
Range, step
Default value
R/W
0: No limitation
1: Continuous
2: Digital inputs
R/W
0: Current
1: Power
R/W
0~50 A, step: 1 A
50 A
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
R/W
-5~5°C, step: 0,5°C
0°C
R/W
0: Manual
1: Automatic
R/W
0: No
1: Yes
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
35°C
R/W
[9-05]~[9-06]°C, step: 1°C
50°C
R/W
10~25°C, step: 1°C
15°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
[9-07]~[9-08]°C, step: 1°C
8°C
R/W
[9-07]~[9-08]°C, step: 1°C
12°C
R/W
25~43°C, step: 1°C
35°C
R/W
10~25°C, step: 1°C
20°C
R/W
35~[6-0E]°C, step: 1°C
55°C
R/W
45~[6-0E]°C, step: 1°C
60°C
R/W
10~25°C, step: 1°C
15°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
10~25°C, step: 1°C
15°C
R/W
[9-01]~[9-00], step: 1°C
35°C
R/W
[9-01]~min(45, [9-00])°C, step: 1°C
25°C
R/W
0: Disabled
1: Enabled
R/W
0: Disabled
1: Enabled
R/W
10~25°C, step: 1°C
20°C
R/W
25~43°C, step: 1°C
35°C
R/W
[9-03]~[9-02]°C, step: 1°C
22°C
R/W
[9-03]~[9-02]°C, step: 1°C
18°C
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
R/W
3~66°C, step: 1°C
5°C
R/W
3~10°C, step: 1°C
5°C
R/W
3~10°C, step: 1°C
5°C
R/W
3~10°C, step: 1°C
5°C
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
R/W
0: No
1: Yes
R/W
0~23 hour, step: 1 hour
1
R/W
60°C
R/W
40~60 min, step: 5 min
40 min
R/W
4~16°C, step: 1°C
12°C
R/W
0: Disabled
1: Enabled
(*1) Only applicable for models where cooling is possible
Installer setting at variance with
default value
Date
Value
(*2) EHFH03S18D▲3V▼