Daikin Altherma EHFH03S18D 3V Series Installer's Reference Manual page 21

Table of Contents

Advertisement

ERLA03D + EHFH03S18D
Daikin Altherma 3 R F
4P596806-1C – 2022.09
WARNING
Prevent hazards due to inadvertent resetting of the thermal cut-out: power to this
appliance MUST NOT be supplied through an external switching device, such as a
timer, or connected to a circuit that is regularly turned ON and OFF by the utility.
WARNING
Air purging heat emitters or collectors. Before you purge air from heat emitters or
collectors, check if an error or
interface.
If not, you can purge air immediately.
If yes, make sure that the room where you want to purge air is sufficiently
ventilated. Reason: Refrigerant might leak into the water circuit, and
subsequently into the room when you purge air from the heat emitters or
collectors.
Disposal (see
"15 Disposal" [
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump down the system, and there
is a leak in the refrigerant circuit:
Do NOT use the unit's automatic pump down function, with which you can collect
all refrigerant from the system into the outdoor unit. Possible consequence: Self-
combustion and explosion of the compressor because of air going into the
operating compressor.
Use a separate recovery system so that the unit's compressor does NOT have to
operate.
3
Specific installer safety instructions
|
is displayed on the home pages of the user
4
 195])
Installer reference guide
21