Commissioning
6.5 Local commissioning
Lower warning limit
Sets the lower warning limit. A diagnostic is generated if the process value falls below this
limit.
Setting
Default
Hysteresis
Sets hysteresis for alarm and warning limits. Hysteresis is distance between limits for
activation and deactivation of an alarm/warning.
Setting
Default
Step: Configure relays?
Configure relays?
Allows user to configure relays if required for application.
Select "Yes" to assign a relay output to the alarm. Select "No" to configure alarms only for the
local display, communication interface, and diagnostic log.
Setting
Default
NOTICE
Relay configuration overwritten by Alarms wizard
It is recommended to complete the wizard prior to any manual parameter adjustments, as
relay settings configured in the Alarms wizard will supersede any relay settings previously
configured outside of the wizard.
96
-99999 ... 99999 m
0.0 m
0 ... 99999 m
0.1 m
Yes
Continue to next step to configure relays.
No
Skip step to configure relays, and go to last step in wizard.
Yes
SITRANS LT500 with ultrasonic transducer inputs
Compact Operating Instructions, 02/2024, A5E52021877-AA