Optex AIR-SLIDE T Manual page 2

Advertisement

Adjustments
1. Area angle adjustment (1st to 6th rows)
1-1.Depth angle adjustment
When adjusting the 2nd row close to the door,
see dipswitch 16 in Table 1 for
the easier adjustment.
-8°
Shallow
1-2.Width angle adjustment
Width angle of the detection area can be adjusted 7° either left or right in 2 steps.
3.5°×2
3.5°×2
Right
Left
2. Width pattern adjustment (1st to 6th rows)
Width pattern adjustment screw should be used to set the width pattern.
1
2
Left
eliminated
NOTE
When setting the width pattern, make sure to turn the
width pattern adjustment screws until it clicks.
3. Area angle adjustment (FLEX EYE)
Make sure to adjust the FLEX EYE angle depending on the door type and the intended touchless plate position otherwise
the sensor may not detect when a hand is approached.
3-1.Depth angle adjustment
-14°
+2°
Shallow
Deep
NOTE
After adjusting the angle, make sure that the FLEX EYE is placed on the proper position for your use.
Attach the touchless plate on the appropriate position after adjusting the FLEX EYE.
CAUTION
Risk of getting caught
Make sure to attach the touchless plate where a hand is not caught
by the door during door opening and closing.
3-2.Width angle adjustment
6°×7
6°×7
Right
Left
4. Dipswitch settings
Table 1
No.
Function
Setting
Low
High
Sensitivity
1
1
1
2
30sec.
60sec.
Presence timer
3
2
3
2
3
Setting 1
Setting 2
4
Frequency
5
4
5
4
5
6rows
5rows
6
Depth row
adjustment
7
6 7
6 7
OFF
ON
Immunity
8
8
8
N.O.
N.C.
Activation output
9
9
9
N.O.
N.C.
10
Safety output
10
10
High
Low
11
Test input
11
11
1st to 3rd
All rows
rows
12
Presence area
12
12
Low
High
FLEX EYE
13
sensitivity
13
13
ON
OFF
FLEX EYE
14
mode
14
14
OFF
ON
15
BLUEZONE
15
15
OFF
ON
Installation mode
16
16
16
[feet,inch (m)]
Deep
Shallow
6 ' 7 " (2.0)
9 ' 10 " (3.0)
9'10"
6'7"
3'3"
0
6'7"
(3.0)
(2.0)
(1.0)
(2.0)
+8°
NOTE
Make sure that the detection area does not
overlap with the door/header, and there is
Deep
no highly reflecting object near the detection
area otherwise ghosting/signal saturation
may occur.
[feet,inch (m)]
Left
Right
6 ' 7 " (2.0)
9 ' 10 " (3.0)
6'7"
3'3"
0
3'3"
(2.0)
(1.0)
(1.0)
Front view
7
8
6'7"(2.0)
Right
1
2
3 4 5
eliminated
9'10"(3.0)
6'7"
3'3"
(2.0)
(1.0)
1 2
cannot be eliminated separately, neither can
Operation
indicator : Purple
Double slide door
Single slide door
3"
(0.08)
[feet,inch(m)]
Comment
Set dipswitch 1 to "Low" when the sensor
installed under 8'2" height.
This height is reference only. Adjust sensitivity
according to your risk assessment.
1st - 3rd rows have the presence detection
180sec.
600sec.
function. The presence timer can be selected
from 4 settings. To enable the presence
detection, do not enter the detection area for
2
3
2
3
10 s after setting the timer.
Make sure to select different frequency setting
Setting 3
Setting 4
for interior and exterior sensors. When using
more than one sensor close to each other,
4
5
4
5
set the frequency different for each sensor.
4rows
3rows
The number of depth rows can be selected
from 4 patterns.
6 7
6 7
Set dipswitch 8 to "ON" when the sensor
operates by itself (Ghosting).
Select "N.O."/"N.C." for activation output to
door controller.
Select "N.O."/"N.C." for safety output to
door controller.
Select "High"/"Low" for test input from door
controller. The delay time between test input
and safety output is 10 ms.
When dipswitch 12 is set to "All rows",
1st - 6th rows have presence detection
function.
Adjust sensitivity for FLEX EYE.
Select the FLEX EYE mode "ON" or "OFF".
ON : Activation output is emitted when a
detection occurs in FLEX EYE and the 2nd to
4th row.
OFF : Activation output is emitted when a
detection occurs in the 2nd to 6th row.
When dipswitch 15 is set to "ON", the
BLUEZONE (1st row) is active and looks
through the threshold.
Set dipswitch 16 to "ON" to adjust the 2nd row.
During the installation mode only the 2nd row
remains active and the operation indicator
shows Yellow. After setting the row, set
dipswitch 16 to "OFF".
Checking
Check the operation according to the chart below.
[feet,inch (m)]
Entry
Image
3'3"
0
3'3"
(1.0)
(-1.0)
Status
Operation indicator
9
N.O.
Activation
output (*1)
9
N.C.
10
N.O.
Safety
output
10
N.C.
[feet,inch (m)]
Entry
Image
3'3"
0
3'3"
6'7"
(1.0)
(1.0)
(2.0)
Status
[feet,inch (m)]
Operation indicator
9
N.O.
Activation
output (*1)
9
N.C.
10
N.O.
Safety
output
10
N.C.
6
7
8
0
3'3"
6'7"
NOTE
(1.0)
(2.0)
- Do not enter the detection area during set-up.(Operation indicator : Yellow blinking)
7 8
.
- The response time may differ according to the color of the objects and the color/material of the floor.
*1 : Activation output shows the status of when FLEX EYE mode is enabled. (dipswitch 14 is set to "ON".)
Inform building owner/operator of the following items
WARNING
1. Do not wash the sensor with water.
2. Do not disassemble, rebuild or repair the sensor yourself, otherwise electric shock may occur.
CAUTION
1. Do not paint the detection window.
NOTE
1. Always keep the detection window clean. If dirty, wipe the window with a damp cloth.
Do not use any cleaner/solvent.
2. When the operation indicator blinks Green, contact your installer or service engineer.
3. Always contact your installer or service engineer when changing the settings.
4. When turning the power ON, always walk-test the detection area to ensure the proper operation.
5. Do not place any objects that move or emit light in the detection area. (e.g. Plant, illumination, etc.)
Troubleshooting
Operation
Door operation
indicator
None
Door does not
3"
open when a
(0.08)
person enters the
Unstable
detection area
and FLEX EYE.
[feet,inch(m)]
Proper
Door opens when
Proper
a person enters only
the detection area.
Yellow
Door opens when
no one is in the
Unstable
detection area.
(Ghosting)
Proper
Door remains
open.
Fast
Green
blinking
Slow
Green
blinking
Proper operation.
Slow
Purple
blinking
Contact
North and South America Subsidiary
OPTEX INCORPORATED
10741 Walker Rd. Suite 300 Cypress, CA 90630 U.S.A
www.optexamerica.com
Outside of
Entry into
Entry into
Power OFF
detection area
4th to 6th row
Motion
Stand-by
-
detection active
None
Green
Orange
Entry into
Outside of
BLUEZONE
detection area
Motion/Presence
Stand-by
detection active
Blue
Green
Possible cause
Wrong power supply voltage.
Wrong wiring or connection failure.
Wrong detection area(2nd to 4th row) and
FLEX EYE positioning.
Sensitivity of detection area(2nd to 4th row)
is too low.
Sensitivity of FLEX EYE is too low.
Short presence timer.
Dirty detection window.
Wrong wiring or connection failure.
FLEX EYE function is not working.
(Dipswitch 14 is set to "OFF")
Installation mode is set to "ON".
Objects that move or emit light in the
detection area and FLEX EYE.
The detection area and FLEX EYE
overlaps with those of another sensor.
Waterdrops on the detection window.
The detection area overlaps with the
door/header.
Sensitivity of detection area is too high.
Sensitivity of FLEX EYE is too high.
Others
Wrong setting of dipswitches.
Sudden change in the detection area.
Wrong wiring or connection failure.
Sensitivity of detection area is too low.
Sensitivity of FLEX EYE is too low.
Dirty detection window.
Sensor failure.
Signal saturation.(detection area)
The detection area overlaps with the
door/header.
Signal saturation. (FLEX EYE)
FLEX EYE overlaps with the header.
Tel : +1(800)877 6656
Entry into
Entry into
FLEX EYE and
3rd row
2nd row
2nd to 4th row
Motion/Presence detection active
Red
Red blinking
Purple
Entry into
FLEX EYE only
Motion
detection active
Fast Purple blinking
Possible countermeasures
Set to the stated voltage.
Check the wires and connector.
Check the detection area and FLEX EYE
(Adjustment 1,2,3) and depth row
adjustment (dipswitch 6,7).
Set the detection area sensitivity higher
(dipswitch 1).
Set the FLEX EYE sensitivity higher
(dipswitch 13).
Set the presence timer longer
(dipswitch 2,3).
Wipe the detection window with a damp
cloth. Do not use any cleaner or solvent.
Check the wires and connector.
Set dipswitch 14 to "ON".
Set dipswitch 16 to "OFF".
Remove the objects.
Check the frequency setting (dipswitch 4,5).
Use the rain-cover (Separately available).
Wipe the detection window with a damp
cloth. Do not use any cleaner or solvent.
Install in a place keeping the waterdrops off.
Adjust the detection area to "Deep"(outside).
Set the detection area sensitivity lower
(dipswitch 1).
Set the FLEX EYE sensitivity lower
(dipswitch 13).
Set dipswitch 8 to "ON".
Check the activation output(dipswitch 9) or
safety output(dipswitch 10) or test input
(dipswitch 11).
Check sensitivity or presence timer
(dipswitch 1,2,3).
If the problem still persists, hard-reset the
sensor.(Turn the power OFF and ON again.)
Check the wires and connector.
Set the detection area sensitivity higher
(dipswitch 1).
Set the FLEX EYE sensitivity higher
(dipswitch 13).
Wipe the detection window with a damp
cloth. Do not use any cleaner or solvent.
Contact your installer or service engineer.
Remove highly reflecting objects from the
detection area. Or lower the detection area
sensitivity(dipswitch 1).
Or change the detection area depth angle.
Adjust the detection area to "Deep" (outside).
Remove highly reflecting objects from the
FLEX EYE. Or lower the FLEX EYE
sensitivity (dipswitch 13). Or change the
area depth angle for FLEX EYE.
Adjust FLEX EYE to "Deep" (Outside).
Manufacturer