Mounting Pressure-Tight Probe Of Ee310-T10; Installation Of The Probe Directly In The Process - E+E Elektronik EE310 User Manual

High-end humidity and temperature sensor for industrial applications
Hide thumbs Also See for EE310:
Table of Contents

Advertisement

The stainless steel mounting flange is not appropriate for pressure-tight mounting. For pressure-tight
requirements, use EE310-T10.
For probe hanging on its cable from the ceiling in applications where condensation is likely to happen, it is
important to avoid condense water getting from the cable to the probe and into the sensing head. For this
purpose, use the drip water protection (see 8 Spare Parts and Accessories).
4.5

Mounting Pressure-Tight Probe of EE310-T10

WARNING
General safety instructions for pressure-tight installation
The installation, commissioning and operation of the EE310-T10 may be performed by qualified staff
only. Special attention shall be paid to the correct installation of the probe into the process. In case of
inappropriate installation there is the risk for the probe to be suddenly expulsed due to the pressure in the
process.
Bending over the sensing probe should be avoided under any circumstances!
Make sure that the surface of the probe is not damaged during installation. A damaged probe surface may
lead to damaged seals and consequently to leakage and pressure loss.
The probe is rated with leakage rate B according to EN12266-1.
4.5.1.

Installation of the Probe Directly in the Process

NOTICE
For direct probe installation shut-off valves shall be placed on both sides of the probe insert (see Fig. 10
Installation of the EE310-T10 probe directly into the process). This allows the sensor probe to be easily
removed for maintenance and calibration.
For direct installation into a pressure chamber make sure that the pressure in the chamber and the ambient
pressure are equal before removing the probe. The temperature during probe installation may deviate by
max. ±40 °C (±72 °F) from the regular temperature during normal operation.
Replace the metal sealing ring (see Fig. 10) by a new one every time before re-installing the probe.
Probe installation steps
1.
Close both shut-off valves.
2.
Place the sensor probe into the probe insert and adjust the immersion depth.
3.
Tighten the lock nut with a torque of 30 Nm.
4.
Open the shut-off valves.
WARNING
Strictly observe the tightening torque. A torque lower than 30 Nm results in a smaller retention force of the
clamping sleeve. This leads the risk of sudden expulsion of the sensing probe due to the pressure. A torque
higher than 30 Nm may lead to permanent deformation of the clamping sleeve and the sensing probe. This
would make the removal and re-installation of the probe difficult or even impossible.
User Manual EE310