Ipv4 Settings - E+E Elektronik EE310 User Manual

High-end humidity and temperature sensor for industrial applications
Hide thumbs Also See for EE310:
Table of Contents

Advertisement

UDP (Port 5234)
Backwards compatible communication protocol with EE31 device series. Communication via
Ethernet takes place by means of UDP packets, which transport a command or a command response
in EE31 protocol format as payload data. See "Ethernet - communication protocol" available at
www.epluse.com/en/service-support/download-center.
5.6.2.

IPv4 Settings

Factory setting
IP Address
Subnet Mask
Gateway
DNS
Tab. 15 IPv4 settings
DHCP options can be set with jumper on the PCB.
Factory setting: DHCP disabled (static IP). Please refer to Fig. 24 below.
Fig. 24
Ethernet Module - DHCP setting
The setup of the Modbus TCP communication can be performed via PCS10 Product Configuration Software or via
display and push buttons (see 11 Appendix, Fig. 48 IP settings).
Changing the IP address via PCS10 or the display is only possible if the DHCP jumper is set to "Static".
Otherwise the IP settings are read-only.
NOTICE
Supported Ethernet standard: 802.3i/u/x and af.
IPv6 is not supported.
192.168.0.64
255.255.255.0
192.168.0.1
192.168.0.1