12-8. Power Required To Start Motor
Motor Start
G
Code
KVA/HP
6.3
12-9. How Much Power Can Generator Supply?
OM-252624 Page 76
Single-Phase Induction Motor Starting Requirements
H
J
7.1
8.0
4
AC MOTOR
1
VOLTS
230
AMPS
3
CODE
M
Hz
HP
1/4
PHASE
1
2
K
L
9.0
10.0
2
2.5
60
1
M
N
11.2
12.5
1
Motor Start Code
2
Running Amperage
3
Motor HP
4
Motor Voltage
To find starting amperage:
Step 1: Find code and use table to
find kVA/HP. If code is not listed,
multiply running amperage by six to
find starting amperage.
Step 2: Find Motor HP and Volts.
Step 3: Determine starting amper-
age (see example).
Welder/generator amperage output
must be at least twice the motor's
running amperage.
(kVA/HP x HP x 1000) / Volts =
Starting Amperage
Example: Calculate starting amper-
age required for a 230 V, 1/4 HP mo-
tor with a motor start code of M.
Volts = 230, HP = 1/4, kVA/HP =
11.2
(11.2 x 1/4 x 1000) / 230 = 12.2A
Starting the motor requires 12.2
amperes.
1
Limit Load To 90% Of
Generator Output
Always start non-resistive (motor)
loads in order from largest to small-
est, and add resistive loads last.
2
5 Second Rule
If motor does not start within 5
seconds, turn off power to prevent
motor damage. Motor requires
more power than generator can
supply.