SPECIFICATIONS SUMMARY
For a full list of compatible panel accessories, refer to "Ordering Information".
Power Supply
Transformer Input—Primary input: 120 VAC 60 Hz; Primary Output: 16 VAC 56 VA
Standby Battery—12 VDC, 1.0 Amps Max. charging current
Smoke and Auxiliary—12 VDC output at 0.5 Amp Max
Bell Output—12 VDC at 0.7 Amp Max
The combined Auxiliary and Bell outputs total cannot exceed 1.2 Amps with a 56 VA transformer. All circuits are power
limited except the red battery wire and AC terminal.
Communication
•
Built‑in network communication to SCS‑1R and SCS‑VR Receivers
•
Built‑in dialer communication to SCS‑1R Receivers
•
Optional cellular communication to SCS‑1R and SCS‑VR Receivers
•
Built‑in Contact ID communication to SCS‑1R Receivers
•
Optional 893A Dual Phone Line Module with phone line supervision
•
Can operate as a local panel
Panel Zones
Eight 1k or 2.2k Ohm EOL burglary zones (1‑8) and two 3.3k Ohm EOL powered zones with reset (9‑10). To select either
1k or 2.2k for zones 1 to 8, program the EOL value in REMOTE OPTIONS.
Keypad Bus
You can connect the following supervised keypads and expansion modules to the Keypad Bus:
•
Alphanumeric keypads
•
Sixteen, eight, four, and single‑zone expansion modules
•
Single zone detectors
•
Access control modules
LX‑Bus
You can connect the following devices to the LX‑Bus connections provided on the panel. See Accessory Devices for
information about specific connections.
•
Graphic annunciator modules
•
Sixteen, eight, four, and single‑zone expansion modules
•
Relay output expansion modules
•
Smoke Detectors
Outputs
The XR150FC/XR550FC Series panel provides two Single Pole, Double Throw (SPDT) relay outputs which require
the installation of two Model 305 relays, each rated 1 Amp at 30 VDC resistive (power limited sources only). A
Model 431 Output Harness is required to use these outputs.
The panel also provides four open collector outputs rated for 50 mA each. The open collector outputs provide ground
connection for a positive voltage source. A Model 300 Output Harness is required to use these outputs.
Digital Monitoring Products
2