SPECIFICATIONS SUMMARY

For a full list of compatible panel accessories, refer to "Ordering Information".

Power Supply

Transformer Input—Primary input: 120 VAC 60 Hz; Primary Output: 16 VAC 56 VA
Standby Battery—12 VDC, 1.0 Amps Max. charging current
Smoke and Auxiliary—12 VDC output at 0.5 Amp Max
Bell Output—12 VDC at 0.7 Amp Max
The combined Auxiliary and Bell outputs total cannot exceed 1.2 Amps with a 56 VA transformer. All circuits are power
limited except the red battery wire and AC terminal.

Communication

Built‑in network communication to SCS‑1R and SCS‑VR Receivers
Built‑in dialer communication to SCS‑1R Receivers
Optional cellular communication to SCS‑1R and SCS‑VR Receivers
Built‑in Contact ID communication to SCS‑1R Receivers
Optional 893A Dual Phone Line Module with phone line supervision
Can operate as a local panel

Panel Zones

Eight 1k or 2.2k Ohm EOL burglary zones (1‑8) and two 3.3k Ohm EOL powered zones with reset (9‑10). To select either
1k or 2.2k for zones 1 to 8, program the EOL value in REMOTE OPTIONS.

Keypad Bus

You can connect the following supervised keypads and expansion modules to the Keypad Bus:
Alphanumeric keypads
Sixteen, eight, four, and single‑zone expansion modules
Single zone detectors
Access control modules
LX‑Bus
You can connect the following devices to the LX‑Bus connections provided on the panel. See Accessory Devices for
information about specific connections.
Graphic annunciator modules
Sixteen, eight, four, and single‑zone expansion modules
Relay output expansion modules
Smoke Detectors

Outputs

The XR150FC/XR550FC Series panel provides two Single Pole, Double Throw (SPDT) relay outputs which require
the installation of two Model 305 relays, each rated 1 Amp at 30 VDC resistive (power limited sources only). A
Model 431 Output Harness is required to use these outputs.
The panel also provides four open collector outputs rated for 50 mA each. The open collector outputs provide ground
connection for a positive voltage source. A Model 300 Output Harness is required to use these outputs.
Digital Monitoring Products