Function Test,
cont.
Step Time
11
12
13
14
15
16
Fire & smoke alarm
Once the self-test has been completed, a fire and smoke alarm test (if applicable) should be
carried out.
Fire and smoke alarm
Activate the
fire/smoke alarm
Signature
Site / station designation
Function test
Go to self-test point manual point Fans start the fan
Go to alarm menu
Check that alarm Filterguard 1 in the display have a highlighted alarm icon
(s)
120
Alarm 5, low supply voltage 42VDC
NC, check it is change to NO (multimeter)
120
Alarm 6, high voltage 60VDC
NC, check it is change to NO (multimeter)
120
Alarm 7, Room temperature sensor
NC, check it is change to NO (multimeter)
120
Alarm 8, Outdoor temperature sensor
NC, check it is change to NO (multimeter)
120
Alarm 9, high temperature alarm (40°C)
NC, check it is change to NO (multimeter)
120
Alarm 10, High humidity alarm (if installed)
NC, check it is change to NO (multimeter)
Alarm
The fire and smoke alarm must be connected to digi-
tal 1, it is important that the smoke alarm have a dry
contact (potential free)
Check that Fans, heater, Air cons etc stops immedi-
ately and there ia an alarm at alarm No 3
Test date
Test carried out by
Signature
Company
Activity
Activity
Test report information
Result
Result