Dantherm TKS 60 Service Manual page 24

Hide thumbs Also See for TKS 60:
Table of Contents

Advertisement

Comfort mode
The fan is limited to idle speed in comfort mode.
If you want to change set point and duration this can be changed by pressing enter when
the cursor has highlighted the menu line.
Servicing interval
Dantherm recommends the unit to be serviced at least once a year. We also recommend
that the unit is inspected during the initial service to determine if the servicing interval is too
long. We recommend that preventive maintenance is carried out during spring.
Warranty
The factory warranty only applies if servicing has been carried out and documented at an in-
requirements
terval of a maximum of one year. The documentation may be a written log.
Preventive
The recommended procedure for preventive maintenance is:
maintenance
Select
and press enter.
If this is OK press arrow down two times and when cursor is on Disable/enable press
enter.
Press arrow down one time and then enter to exit this submenu.
Step
1
Make sure that the power supply to the unit has been safely turned off.
2
Remove the old filter and carefully clean the unit.
3
Clean the dampers and check that they work and close tightly.
4
Clean the fan and check its attachment.
5
Check and clean the air intake and ventilation accessories.
6
Carefully fit the new filter.
7
Close the unit and ensure that all servicing has been carried out correctly.
8
Turn on the power to the unit.
9
Run the self-test in accordance with the separate control unit manual.