Function Test

Introduction
After connecting the free cooling unit, the display normally shows the current room temper-
ature.
The following test must be carried out to ensure that the system works. Each test phase must
be acknowledged with a signature and a date. This is to maintain the warranty and to pro-
vide documentation prior to future servicing.
NB Before starting the unit, check that there is no protective paper blocking the filter. If the
filter is blocked, air flow is stopped, and a filter alarm is given.
Start a self-test
First check the home menu.
If the indoor and outdoor temperature sensors show unexpected temperatures
check their location and condition. Move or replace if necessary.
Check for any alarms.
Press down arrow twice and if any alarm is highlighted.
If no alarms are activated go to self-test
To start a self-testcard press down arrow 4 times and then enter.
An automatic self-test can be carried out by pressing enter when the cursor is on Stop/start.
A manual test can be carried out by using the arrow buttons to navigate the menu to the
specific test point that needed to be tested.
Automatic test
Step
10
Time
(s)
1
120
Damper to outdoor opens (if installed)
Check visually that the damper is open
2
120
Fan runs 75% of max rpm
Check that the fan(s) ramp up
3
120
Damper to outdoor close (if installed)
Check visually that the damper is closed
4
120
Electrical heater is active (if installed)
Check that the heater is hot
5
120
Air conditioner 1 is active (if installed)
Check the Air conditioner 1 starts
6
120
Air conditioner 2 is active (if installed)
Check the Air conditioner 2 starts
7
120
Alarm 1, Fan 1 alarm
NC, check it is change to NO (multimeter)
8
120
Alarm 2, Alarm for clogged filter
NC, check it is change to NO (multimeter)
9
120
Alarm 3, Digital 1 fire alarm (if installed to digital 1)
NC, check it is change to NO (multimeter)
120
Alarm 4, low temperature 10°C
NC, check it is change to NO (multimeter)