Energy save Mode (Freecooling > A/C)
If outdoor temperature is less than 1°C colder than indoor room temperature the Fan will stop. The connected
Air-con units will start and stop according to the table above.
Description
Off
temperature when fan stops
On
Temperature when Fan starts
Min °C
temperature at bottom of P-band
Max °C
Temperature at top of P-band
The wanted indoor temperature;
Set Point
fan speed will be adjusted be-
tween Min°C and Max °C
A/C 1 on
External Air Con unit 1 start if connected
A/C 1 off
External Air Con unit 1 stops if connected
A/C 2 on
External Air Con unit 2 start if connected
A/C 2 off
External Air Con unit 2 stops if connected
Emergency on
Fan run 100% and both A/C 1 and A/C 2
starts
Emergency off
Fan stops both A/C 1 and A/C 2 continue
to run
Value
20
23
25
29
27
31
29
33
31
38
36
22