may also be connected. The locking actuators' power consumption is not included in the calculated 6A as the
actuators and locking actuators do not run simultaneously.
All actuators on the same motor line run/are operated at the same time.
All actuators on a motor line must be the same type.
Connection / cable diameter: flexible max 6 mm² / solid max 10 mm².
Cable length: see the chapter "Cable dimensioning".
Standard
actuators
±24V
Example with max. 3A current
consumption
a) 3 pcs. WMX 826-1
b) 2 sets of 3 pcs. WMX 504-3
c) 1 pc. WMU 883-1
d) 2 pcs. WMU 861-2
MotorLink
®
actuators
Examples with actuators per
motor line
Ex. 1: 4 pcs. WMX 823-1
Ex. 2: 2 pcs. WMX 836-2
Ex. 3: 3 pcs. WMU 826-3
Allowed actuator combinations on a MotorLink
The two motor lines can each be connected to one of the below shown combinations.
-1 (single): one window with one single window
actuator. Up to four windows each with one
single window actuator can be connected
-2 (double): one window with two double
window actuators.
-3 (triple): one window with three triple window
actuators.
-4 (quad): one window with four quad window
actuators.
Connecting variants to standard actuators on motor line 1
®
motor line
11