Connection description

9
On the WCC 106 A the following
can be connected: ±24V
standard actuators, MotorLink®
actuators, comfort keypad,
thermostat and similar plus wind
/ rain sensor.
X1
WCC 106 A contains two motor lines to which ±24V standard actuators or MotorLink® actuators can be
connected. The two motor lines must run with the same type of actuators, meaning either ±24V standard
actuators or MotorLink® actuators. When running MotorLink® actuators, DIP switch #5 must be set, see chapter
about DIP switches for details.
±24V standard actuators
Data:
1.1 24V / 0V
1.2
1.3 0V / 24V
1.4 24V / 0V
1.5
1.6 0V / 24V
The number of permitted actuators on the motor line depends on the actuator type. The total current
consumption connected to the motor line may not exceed 6A and the total current consumption for both motor
lines may not exceed 6A incl. load on X7 (AUX). In addition to the actuators, locking actuators of type WMB 8xx
}
motor line #1
}
motor line #2
®
MotorLink
actuators
Data:
1.1 0V
1.2 Communication
1.3 24V
1.4 0V
1.5 Communication
1.6 24V
10
}
motor line #1
}
motor line #2