5.5
Securing the burner to the boiler
For the installation proceed as follows:
Fix the burner 1)(Fig. 9) to the boiler door 2) using the 4
screws and (if necessary) the 4 nuts supplied to the stand-
ard equipment, interposing the insulating gasket 3).
D10488
5.6
Positioning the probe - electrode
Before installing the burner on the boiler, make sure the probe
and electrode are placed correctly as in Fig. 10.
20028767
Installation
2
3
1
Do not turn the electrode: position it as illustrated.
Placing the electrode near the ionisation probe
may result in the control box amplifier being dam-
aged.
WARNING
4÷ 5 mm
D10489
12
GB
Fig. 9