Training manual ALTEAS & GENUS ONE

2 OPERATING LOGIC

2.1

FIRST IGNITION PROCEDURE

The boiler is equipped with an automatic combustion control system that allows to the boiler to auto-regulate
the combustion. This is possible using the feed-back that comes from the ionization current and adjusting the
gas through the gas valve.
After the installation of the boiler it needs to do the Automatic calibration procedure, because the boiler has
to adjust the combustion taking in account the gas (type, quality and pressure) and exhaust/air pipes length.
During the Automatic calibration procedure, the boiler must be with frontal panel closed and the air/flue ducts
completely assembled.
This is the procedure:
Switch on the boiler and the display shows the
1
calibration warning.
Purge of the hydraulic system using "Air purge
2
function" from the "Configuration wizard" menu.
Using the specific parameter enable the
"Automatic calibration" (Technical area > Service >
3
Automatic calibration).
Automatic calibration – Step 1:
Gas type selection:
 0 : Natural gas (factory setting)
 1 : LPG
 2 : G230
4
 3 : G130
Press "OK" button to start the calibration.