Menù 6 : Zone 3 Parameters - Ariston ALTEAS ONE Training Manual

Wall hang boilers, condensation compact
Table of Contents

Advertisement

Training manual ALTEAS & GENUS ONE
Pump fixed speed setting (with
5
4
2
9.3.5
Menù 6 : Zone 3 parameters
6
0
SETPOINT
6
0
2
Temperature setpoint zone 3
6
2
ZONE 2 SETTING
Select high or low temperature
6
2
0
Thermoregulation mode
6
2
1
6
2
2
Select thermoregulation curve
Select thermoregulation curve
6
2
3
Influence of the room probe on
6
2
4
Zone 3 maximum heating
6
2
5
Zone 3 minimum heating
6
2
6
6
3
DIAGNOSTICS
Zone 3 delivery temperature
6
3
2
6
3
3
Zone 3 return temperature (°C)
6
3
4
Heating request by zone 3
6
3
5
6
4
ZONE 3 ZONE MODULE SETTINGS
6
4
0
Zone 3 pump modulation
ΔT for pump modulationa
6
4
1
Pump fixed speed setting (with
6
4
2
par. 540 = 0)
Function
for zone 3
selection
parallel shifting
thermoregulation
temperature (°C)
temperature (°C)
(°C)
Zone 3 pump status
par. 640 = 0)
20 ÷ 100
Range
Par 425 ÷ Par 426
0: low temperature
1: high temperature
0: fixed delivery temperature
1: basic thermoregulation
2: only room probe
3: only outside probe
4: room probe + external probe
0_2 ÷ 1_0 (par. 420=0)
1_0 ÷ 3_5 (par. 420=1)
(with Auto function enabled)
-7 ÷ 7 (par. 420=0)
-14 ÷ 14 (par. 420=1)
(with Auto function enabled )
0 ÷ 20
(with Auto function enabled )
20 ÷ 45 (par. 420=0)
35 ÷ 82 (par. 420=1)
20 ÷ 45 (par. 420=0)
35 ÷ 82 (par. 420=1)
(only visualization)
(only visualization)
OFF: no
ON: yes
(only visualization)
OFF: switch-off
ON: switch-on
(only visualization)
(visible only with zone module connected)
0: Fix
1: Modulating (ΔT)
2: Modulating (pressure)
4 ÷ 25
20 ÷ 100
100
Default
setting
/
1
1
0_6 (par 420=0)
1_5 (par 420=1)
0
20
45 (par. 420=0)
82 (par. 420=1)
20 (par. 420=0)
35 (par. 420=1)
/
/
/
/
1
7 (par. 420=0)
20 (par. 420=1)
100
Page. 81 of 88