Complete Menu; Menù 0 : Network; Menù 2 : Boiler Parameter - Ariston ALTEAS ONE Training Manual

Wall hang boilers, condensation compact
Table of Contents

Advertisement

Training manual ALTEAS & GENUS ONE
9.3

COMPLETE MENU

9.3.1
Menù 0 : Network
0
2
BUS NETWORK
0
2
0
Network presence in the bus
0
4
USER INTERFACE
0
4
0
Zone to be set by display
0
4
1
Thermoregulation button
0
4
2
9.3.2
Menù 2 : Boiler parameter
2
0
GENERAL
2
0
0
DHW setpoint temperature
2
0
2
Gas Type
2
2
GENERAL
Slow ignition as % of the
2
2
0
maximum heating power
Floor thermostat or Room
2
2
3
thermostat zone 2 selection
2
2
4
2
2
5
Heating delay restart
2
2
8
2
2
9
Boiler nominal power
2
3
CENTRAL HEATING-1
Maximum heating power
2
3
1
(heating absolute maximum
power percentage par. 234) (%)
Function
Backlight time (min)
deactivation
Function
Thermoregulation
Boiler version
Range
(only visualization)
1: heating zone 1
2: heating zone 2
3: heating zone 3
1 ÷ 10 ; 24h
0: Off
1: On
Range
36 ÷ 60
0 : Natural gas
1 : LPG
2 : G230
3 : G130
12kw: 18 ÷ 72
18kw: 33 ÷ 92
24kw: 22 ÷ 61 (18 ÷ 52 for G130)
30kw: 20 ÷ 58
35kw: 21 ÷ 60
0: Floor thermostat
1: Room thermostat zone 2
0: disabled
1: enabled
0: disabled
1: 10 seconds
2: 90 seconds
3: 210 seconds
0: combi
1: Storage with NTC (tank)
2: only heating or storage with
thermostat
3: micro-storage
0 ÷ 100 kW
0 ÷ 100
Default
setting
/
1
24h
0
Default
setting
/
0
See gas
table
0
0
0
Depend on
the boiler
version
Depend on
the boiler
See gas
table
Page. 77 of 88