4 SPECIAL FUNCTIONS

FLUE CLEANER" Function

4.1
This function is used to perform proper boiler combustion analysis and maximum and minimum gas
calibration. Follow the instructions below to enable it:
Press Reset button for 5 continuous seconds
 With the boiler on "Winter" mode, the 3-way valves is positioned on "heating" and the burner turns on
even without heating requested.
 With the boiler on "summer" mode:
o
without sanitary demand the burner turns on in heating;
o
with sanitary demand the burner turns on in sanitary.
 The delivery temperature (NTC1) is checked during the "Flue cleaner" function, as follows:
 "summer" mode → Off: 86°C; On: 81°C;
 "winter" mode → Off: 89°C; On: 84°C.
Four different powers can be selected when the function is enabled:
PRESS
Push the button
> anticlockwise
Push the button
> anticlockwise
To exit the "Flue cleaner" function press the RESET button. However after 30 minutes the function will be
disabled automatically.
PRESS
DISPLAY
The display will show this indication
DISPLAY
POWER
Max sanitary
Minimum
Page. 23 of 88