Ulvac VPC-1100 User Manual page 5

High speed vacuum coater
Table of Contents

Advertisement

Check
capacity
Use a
dedicated
power source
Connect the
ground lead
Warning
Check cable
capacity
Prohibited
Risk of
electrical
shock
Power Supply
Primary power capacity
Three-phase 200 V 30 A+
Single phase 100 V 10 A+
If the power capacity is too low, a sudden power surge may trip the
breaker.
The primary power supply should be used only for this
device, and should not be connected to any other
machinery.
If the breaker capacity is insufficient, a power surge may trip the
breaker.
Connect a D-type earth lead.
200V ground leads are green cables.
100V plugs use a grounded plug. If you are using a plug
adapter, connect the ground lead to the nearest terminal.
If the unit is not properly grounded, you may get an electrical shock
due to a malfunction or short circuit.
If possible, do not use an extension cord. If using one
cannot be avoided, please observe the following
precautions:
Use one of the following power cables:
2
200 V
3.5 mm
+
2
100 V
2.0 mm
+
Using a cable that is too small may cause overheating or start a fire.
Do not place any objects on top of the primary power
cable.
May cause electrical shock or fires.
If the receiving light is lit up, then even after the MAIN
breaker is cut, electricity will still be flowing to the MAIN
breaker. Do not touch the terminal block or other parts.
May cause electrical shock.
B

Advertisement