Installing and connecting a device
5.5 Analog input and digital input/output
Correct wiring of inputs/outputs
The I/O connection must be connected with circuitry that is intended for the configured
behavior. Incorrect wiring can result in a defect of the device.
Analog
input
0 - 10 V DC
For connection to I/O, see section "Connecting interfaces to connecting terminal X4
(Page 26)".
18
Analog
input
24 V DC
4 - 20 mA
For signal "0" 0 V - 5 V
For signal "1" 12 V - 24 V
Digital
input
24 V DC
Equipment Manual, 12/2023, A5E52683268-AE
Digital
output
24 V DC
300 mA
SIMATIC FDE Gateway V1.1