SmartGuard-63A-(S0, AUS0)
User Manual
No.
Cable
Grid AC output power
cable
AC output power cable
for the non-backup load
4
AC output power cable
for the backup load
5
PE cable
6
External WLAN antenna
for the EMMA
Note a: The PE of the SmartGuard-63A-S0 backup power port needs to be connected, but the PE
of the SmartGuard-63A-AUS0 backup power port does not need to be connected.
Issue 03 (2023-12-27)
Type
● Not using the PE
equipotential
bonding point at the
AC output port: two-
core (L and N)
outdoor copper cable
● Using the PE
equipotential
bonding point at the
AC output port:
three-core (L, N, and
PE) outdoor copper
cable
SmartGuard-63A-S0:
three-core outdoor
a
copper cable (L, N, and
PE)
SmartGuard-63A-AUS0:
two-core outdoor
copper cable (L and N)
Single-core outdoor
copper cable and M6
OT terminal
External antenna with
the RP-SMA-J port
NO TE
● The minimum cable cross-sectional area must meet local standards.
● The factors to be considered in cable selection include the rated current, cable type,
routing mode, ambient temperature, and maximum acceptable line loss.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Electrical Connections
Recommended
Specifications
● Conductor cross-
sectional area: ≤ 16
2
mm
● Cable outer
diameter: 10–21
mm
● Conductor cross-
sectional area: ≤ 16
2
mm
● Cable outer
diameter: 10–21
mm
Conductor cross-
sectional area: ≤ 16
2
mm
-
Source
Prepared by
the
customer
Prepared by
the
customer
Prepared by
the
customer
38