Manual or in violation of the current regulations and technical standards. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
To avoid damage to the device, keep the device in the warm environment for at least 1 hour before powering on. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
To configure the module over Ethernet: 1. Connect the Ethernet connector of the device to PC over the Ethernet connection cable (not included). akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
1. Write the new time in the parameter New time. 2. Set the parameter Apply new time = 1 and hold the value for at least 1 second. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
(for mode 4…20 mA) state. The maximum time to go to a safe state after the main power supply fails is 9 seconds. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
To configure the MQTT parameters, open the MQTT group in the parameter tree. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Page 16
3. Single-level wildcard usage MX210/Device/GET/+/COUNTER Obtained value: counter values of all digital inputs. The topic is equivalent to the group of topics: akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
There is no password by default. If you forgot the password, restore the factory settings (Sect. 6). akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
– Signal cables should be routed separately or screened from the supply cables. – Shielded cable should be used for the signal lines. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
The length of the analog output power line must not exceed 30 m. NOTICE Do not connect any wires to NC terminals. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
– The maximum length of the network lines between modules is 100 m. – Both Ethernet connectors can be used. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Page 21
– If the module fails (device error or power supply loss), the data is transferred directly from connector 1 to connector 2 (auto-bypass). Fig. 5.7 Chain topology akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
3. Using a thin tool, press and hold the service button (Fig. 2.2. Pos. 7) for at least 12 seconds 4. Close the cover The device will operate with the default parameters. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
The device should be cleaned with a damp cloth only. No abrasives or solvent- containing cleaners may be used. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Check the device for transport damage and completeness! Report the transport damage immediately to the shipper and akYtec GmbH. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
The test voltages shown in Fig. B.1 correspond to the tests carried out under normal operating conditions with 1 minute exposure time. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Page 28
The replacement should not take longer than one minute. Otherwise, the real-time clock has to be adjusted anew. Fig. C.1 Battery replacement akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Page 29
Voltage 0…3300 0x0321 UINT16 Modbus Slave Safe state timeout 0…60 0x02BC UINT8 Data logging UINT16 Logging interval 10…3600 0x0384 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Page 31
Data address of some or all the required entities are not Illegal Data Address allowed or do not exist in slave akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
Page 32
Value is not accepted by slave Unrecoverable error occurred while slave was attempting to Slave Device Failure perform requested action akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...