1. Overview
MU210-403 is an extension module with 24 relay outputs.
The module operates as a slave in Ethernet network with Modbus TCP
protocol.
The device is intended for use in industrial automation for creation of
decentralized control systems.
2. Environmental conditions
Table 1 Operating conditions
Permissible range
Condition
Ambient temperature
Transportation and storage
Relative humidity
up to 95 % (at +35 °C, non-condencing)
up to 2000 m ASL
Attitude
IP code
Vibration / shock resistance
conforms to IEC 61131-2
EMC emission / immunity
conforms to IEC 61131-2
3. Specifications
Table 2 General specifications
Electrical
Power supply
Power consumption
Polarity protection
Appliance class
Interfaces
Data transfer
Double Ethernet 10/100 Mbps
Protocols
Configuration interface
Digital outputs
Outputs number
Output type
Control
5 A, 250 VAC, resistive load
AC
Switching capacity
DC
Switching current, min.
Switching time
PWM frequency, max.
PWM pulse length, min.
Optional functions
3 A, 30 VDC
Service life, electrical
5 A, 250 VAC
Service life, mechanical
5,000,000 switching cycles
MU210-403_3-EN-130914-1.3
© All rights reserved. Subject to technical changes and misprints.
File size, max.
Number of log files, ,max.
Logging interval, min.
Accuracy
Backup battery
Dimensions
Weight
4. Installation and connection
Before installation make sure there is enough free space for connecting
the module and placing the wires. The module is mounted on a DIN rail
-40...+55 °C
or on a vertical surface using screws.
Installation of external connections is carried out by a wire with a cross
section of not more than 0.75 mm
IP20
For stranded wires, use end sleeves.
After installation, put the wires into the cable channel of the module
housing and close the cover.
If necessary, in order to remove the terminal blocks of the module, loosen
the two screws at the corners of the terminal blocks.
CAUTION
Connection and maintenance is performed only when the
24 (10 ... 48) V DC
module power and the power to all devices connected to it is
9 W at 24 V DC
turned off.
11 W at 48 V DC
Table 3 Network parameters
Yes
II
Parameter
IP address
Subnet mask
Modbus TCP
Gateway
MQTT
SNMP
DNS server 1
NTP
DNS server 2
USB 2.0 (MicroUSB)
Ethernet 10/100 Mbps
5. Wiring
24
Relay, NO
On-Off or PWM
3 A, 30 VDC
10 mA at 5 VDC
15 ms
1 Hz with 0.05 duty cycle
50 ms
Safe state
35,000 switching cycles
50,000 switching cycles
MU210-403
Digital output mudule
Flash-memory (log file storage)
2 kB
1000
10 s
Real time clock
±3 s/day at +25 °С
±10 s/day at -40 °С
CR2032
Mechanical
82 × 124 × 83 mm
approx. 260 g
2
.
Description
Default value
IPv4 Internet Protocol address
192.168.1.99
IP address recognition area in the
255.255.255.0
subnet
IP address of the gateway
192.168.1.1
Primary DNS server
77.88.8.8
Secondary DNS server
8.88.8.8
Fig. 1 Device connectors
,
Fig. 2 Terminal block layout
Table 4
Terminal assignments
Marking
DO1A...DO24A
Relay, NO
Connection to NO contact
DO1B...DO24B
Service button performs following functions:
• Factory settings restore
• IP-address assignment
Fig. 3 Relay wiring
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany
Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
Description

Advertisement

loading
Need help?

Need help?

Do you have a question about the MU210-403 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Akytec MU210-403

  • Page 1 Fig. 3 Relay wiring Service life, mechanical 5,000,000 switching cycles MU210-403_3-EN-130914-1.3 akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany © All rights reserved. Subject to technical changes and misprints. Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
  • Page 2 Fig. 4 Relay wiring (common contact) 6. Settings The module is configured via the Modbus TCP protocol or in the akYtec Tool Pro program via the USB interface (see User Guide). If the module is connected to the USB port, the main module power supply is not required.