MV210-202/204
Digital Input Module
User guide
MV210-202/204_3-EN-43057-2.10
© All rights reserved
Subject to technical changes and misprints
akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MV210-202 and is the answer not in the manual?

Questions and answers

Summary of Contents for Akytec MV210-202

  • Page 1 MV210-202/204 Digital Input Module User guide MV210-202/204_3-EN-43057-2.10 © All rights reserved Subject to technical changes and misprints akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 2: Table Of Contents

    5.2.2. Contact sensor wiring ..................19 5.2.3. PNP/NPN sensor wiring ..................20 5.2.4. Encoder wiring ....................21 5.2.5. Ethernet ......................21 6. Factory settings restoration ....................23 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 3 9. Scope of delivery........................26 Appendix A. Dimensions .......................27 Appendix B. Galvanic Isolation ....................28 Appendix C. Battery replacement ..................29 Appendix D. Modbus Application...................30 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 4: Introduction

    Ensure the mains voltage matches the voltage marked on the nameplate. Ensure the device is provided with its own power supply line and electric fuse. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 5 To avoid damage to the device, keep the device in the warm environment for at least 1 hour before powering on. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 6: Overview

    Plug-in terminal blocks enable quick and easy replacement of the device. Fig. 2.1 Front view (closed cover) Fig. 2.2 Front view (open cover) akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 7 Flashing (0.9 s / 1 s) Ethernet Switch) Input LOW on the input green LEDs HIGH on the input (20) akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 8: Specifications

    ±10 s/day at -40 °С Backup battery CR2032 Mechanical Dimensions 42 × 124 × 83 mm Weight approx. 260 g akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 9: Operating Conditions

    IP code IP20 Vibration / shock resistance conforms to IEC 61131-2 EMC emission / immunity conforms to IEC 61131-2 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 10: Configuration And Operation

    2. Connect the power cable to the removable 2-terminal block and plug it into the device. 3. Power on the device. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 11: Real Time Clock

    3. Set the parameter Apply new time = 0 and hold the value for at least 1 second. The time value cannot be changed more than once per second. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 12: Battery

    If you need to assign IP addresses for several modules, it is more comfortable to use service buttons on devices (Fig. 2.2. Pos. 7), previously having all the modules connected to the PC over Ethernet. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 13: Modbus Slave

    For details on function usage see Modbus specifications. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 14: Digital Inputs

    If the counter overflows, the value is reset. To force a counter reset, write 0 to input value reset register. The counter will be reset within 10 ms after writing the value 0. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 15: Frequency And Period Measurement

    The broker distributes the message to any clients that have subscribed to that topic. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 16: Implementation

    Table 4.8 Topics Topic Parameter Node Function Format Input bitmask MASK UINT Pulse counter value COUNTER DI1…DI20 UINT Example: akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 17: Snmp Protocol

    Parameter Default value Access Enable Enable SNMP connection On / Off Read — public Password for read access community akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 18: Password

    There is no password by default. If you forgot the password, restore the factory settings (Sect. 6). akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 19: Installation

    – Signal cables should be routed separately or screened from the supply cables. – Shielded cable should be used for the signal lines. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 20: General Information

    Common input power supply point SS (MV210-202) 5.2.2 Contact sensor wiring NOTICE The COM/SS circuits are connected inside the device. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 21: Pnp/Npn Sensor Wiring

    Fig. 5.6 Contact sensor wiring (MV210-204) 5.2.3 PNP/NPN sensor wiring Fig. 5.7 PNP sensor wiring (MV210-202) Fig. 5.8 NPN sensor wiring (MV210-202) akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 22: Encoder Wiring

    – The maximum length of the network lines between modules is 100 m. – Both Ethernet connectors can be used. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 23 – If the module fails (device error or power supply loss), the data is transferred directly from connector 1 to connector 2 (auto-bypass). Fig. 5.13 Chain topology akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 24: Factory Settings Restoration

    3. Using a thin tool, press and hold the service button (Fig. 2.2. Pos. 7) for at least 12 seconds 4. Close the cover The device will operate with the default parameters. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 25: Maintenance

    The device should be cleaned with a damp cloth only. No abrasives or solvent- containing cleaners may be used. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 26: Transportation And Storage

    Check the device for transport damage and completeness! Report the transport damage immediately to the shipper and akYtec GmbH! akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 27: Scope Of Delivery

    9 Scope of delivery – MV210–202/204 – Ethernet connection cable – 2-pole plug-in terminal block – Rubber plug – Short guide akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 28: Appendix A. Dimensions

    Appendix A. Dimensions Appendix A. Dimensions Fig. A.1 External dimensions Fig. A.2 Wall mounting dimensions akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 29: Appendix B. Galvanic Isolation

    Appendix B. Galvanic Isolation Appendix B. Galvanic Isolation Fig. B.1 Galvanic isolation akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 30: Appendix C. Battery Replacement

    The replacement should not take longer than one minute. Otherwise, the real-time clock has to be adjusted anew. Fig. C.1 Battery replacement akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 31: Appendix D. Modbus Application

    Voltage 0…3300 0x0321 UINT16 Modbus Slave Safe state timeout 0…60 0x02BC UINT8 Data logging UINT16 Logging interval 10…3600 0x0384 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 32 DI1 Reset value 0 – off / 1 – on 0x00E0 UINT16 … … … … … … … akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 33 Unsigned integer UINT48 Signed integer INT16 String16 String of characters (Win-1251 code page) String32 String of characters (Win-1251 code page) akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 34 Parameter value is beyond the valid limits Invalid data size (valid range 0x07…0xF5) Not specified reference type akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 35 Failed to open the file for writing Nonexistent file requested Read-only file requested Failed to write the required number of bytes akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...