Akytec MU110-24.16R User Manual

Digital output module

Advertisement

Quick Links

МU110–24.16R(K)
Digital output module
User guide
МU110–24.16R(K)_3-EN-143217-1.2
© All rights reserved
Subject to technical changes and misprints
akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de

Advertisement

loading
Need help?

Need help?

Do you have a question about the MU110-24.16R and is the answer not in the manual?

Questions and answers

Summary of Contents for Akytec MU110-24.16R

  • Page 1 МU110–24.16R(K) Digital output module User guide МU110–24.16R(K)_3-EN-143217-1.2 © All rights reserved Subject to technical changes and misprints akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 2: Table Of Contents

    7. Maintenance........................16 8. Transportation and storage ....................17 9. Scope of delivery........................18 Appendix A. Dimensions .......................19 Appendix B. Galvanic isolation ....................21 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 3: Introduction

    If the supply voltage is lower than 20 V DC, the device cannot operate properly but will not be damaged. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 4 To avoid damage to the device, keep the device in the warm environment for at least 1 hour before powering on. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 5: Overview

    – S2 – service function – S3 – DRAM write-protection (see Section 4.9) All DIP switches are in the OFF position by default. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 6: Specifications

    Transportation and storage -25…+55°C Relative humidity up to 80% (at +25°C, non-condensing) Altitude up to 2000 m above sea level akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 7: Configuration And Operation

    38.4 57.6 115.2 Data bits * none even Parity * none PrtY Stop bits * Sbit A.Len Address bits akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 8: Operation Modes

    – Number of bytes, n (0x01…0x02) – Data (bitmask, n bytes). Addressing of individual cells is shown in Table 4.4. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 9: Individual Control In Pwm Mode

    The RS485 serial interface enables communication via a two-wired line in the half-duplex mode. The modules support Modbus RTU and Modbus ASCII protocols. The network consists of a Master akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 10: Modbus Registers

    0…65535 0032 0050 bitmask Table 4.4 Output status binary addresses for Modbus function 15 Address Output Access 0000 0000 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 11: Hardware Write Protection

    3. Set switch S3 to ON. NOTE Switch S3 must be turned off again before changing the module parameters. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 12: Installation

    (COMx) of the same group (see Table 5.1). – In the MU110-24.16K module COMx are group negative terminals. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 13 Power supply RS485 D+ DO10 DO11 DO12 COM1 DO1…DO4 COM3 DO9…DO12 DO13 DO14 DO15 DO16 COM2 DO5…DO8 COM4 DO13…DO16 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 14 If there is inductive load on an NPN output, it is recommended to connect VD diode (100 V, 1 A) to protect the transistor (see Fig. 5.3). Fig. 5.3 MU110-24.16K outputs akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 15: Factory Settings Restoration

    8. The main window of the Configurator opens. Saved user parameters of the module can be read now (see Fig. 6.2). 9. Open folder ‘Network parameters’ and note the user network parameters. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 16 Baud rate 9600 Data bits Parity PrtY None Stop bits Sbit Address bits A.Len Address Addr Response delay, ms Rs.dL akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 17: Maintenance

    The device should be cleaned with a damp cloth only. No abrasives or solvent- containing cleaners may be used. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 18: Transportation And Storage

    Check the device for transport damage and completeness! Report the transport damage immediately to the shipper and akYtec GmbH! akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 19: Scope Of Delivery

    9 Scope of delivery 9 Scope of delivery – Module MU110-24.16R(K) – Short guide akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 20: Appendix A. Dimensions

    Appendix A. Dimensions Appendix A. Dimensions Fig. A.1 External dimensions Fig. A.2 Wall mounting dimensions akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 21 Appendix A. Dimensions Fig. A.3 Replacement of terminal blocks akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 22: Appendix B. Galvanic Isolation

    Appendix B. Galvanic isolation Appendix B. Galvanic isolation Fig. B.1 MU110–24.16R galvanic isolation Fig. B.2 MU110–24.16K galvanic isolation akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...